Operating instructions
Parameterizing steps Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
9-42 Operating Instructions SIMOVERT MASTERDRIVES
P384.02 = ?
Enter the motor load limit 1...300 %
P384.02 = 0
Enter the maximum frequency or speed in positive
direction of rotation in %
The value is referred to P352 (reference frequency) and P353
(reference speed)
P453 = ?
P452 = ?
Enter the maximum frequency or speed in negative
direction of rotation in %
The value is referred to P352 (reference frequency) and P353
(reference speed)
Return to the parameter menu
P060 = 1
Note
When the "Drive settings" menu is exited, the entered
parameter values are checked for their plausibility. Non-
plausible parameter settings result in a fault. The erroneously
set parameters are entered in parameter r949 (fault value).
P128 = ?
Enter the maximum output current in A
P462 = ?
Enter the acceleration time from standstill up to reference
frequency (P352)
P463 = ?
Enter the unit for acceleration time P462
0 = Seconds
1 = Minutes
2 = Hours
P464 = ?
Enter the deceleration time from reference frequency
(P352) up to standstill
P465 = ?
Enter the unit for deceleration time P464
0 = Seconds
1 = Minutes
2 = Hours
no yes
P115 = 2
Sinusoidal filter
(P068=1) or
synchronous motor?
Calculate motor model "Motor identification at standstill"
Note
Current flows through the motor and the rotor rotates!
After pressing the "P" key, the alarm message "A087" appears.
The converter must be turned on within 20 secs!