Operating instructions

Parameterizing steps Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
9-38 Operating Instructions SIMOVERT MASTERDRIVES
The rated frequency P107 and the rated speed P108 automatically
result in the calculation of the pole pair number P109. If the
connected motor is designed as a generator and the generator data
are on the rating plate (oversynchronous rated speed), you have to
correct the pole pair number manually (increase by 1 if the motor is
at least 4-pole), so that the rated slip (r110) can be correctly
calculated.
For induction motors, you have to enter the actual rated motor
speed, and not the synchronous no-load speed in P108, i.e. the slip
frequency at nominal load has to be derived from parameters
P107...P109.
The rated motor slip (1 - P108/60 x P109/P107) should usually be
greater than 0.35 % x P107.
These low values are, however, only achieved in the case of motors
with a very high rating (above approx. 1000 kW).
Motors with average rating (45..800 kW) have slip values around
2.0...0.6 %.
Motors with low rating (below 22 kW) can also have slip values up to
10 %.
It is possible to achieve a more accurate evaluation of the rated slip
after standstill measurement (P115 = 2) by taking into account the
temperature evaluation for the rotor resistance P127.
On cold motors (approx. 20 °C), the value is usually around
70 % (
±
10 %) and on warm motors (operating temperature) around
100 % (
±
10 %). If there are any large differences, you can proceed
on the assumption that the rated frequency P107 or the rated speed
P108 do not correspond to the real values.
If the rated motor frequency (engineered!) is below 8 Hz, you have
to set P107 = 8.0Hz in the drive setting. The rated motor voltage
P101 has to be calculated in the ratio 8 Hz / f
Mot,N
and the rated
motor speed
P108 should result in a much greater slip:
P108 = ((8 Hz - P107
old
) x 60 /
P109) + P108
old
.