Specifications

9
English
L-2254 Installation
Seawater pump is at least one foot below water line and
securely mounted
Strainermountedbelowpumpwithaccesstolter
Double/reversed stainless steel hose clamps on all hose
connections
Threaded seal tape on all threaded connections
Hose runs uphill from speed scoop and sea cock to
strainer, pump and a/c unit, then downhill (if possible)
from a/c unit to overboard discharge
Water owing freely from overboard discharge while
pump is running
Pump relay panel, if used, must have its own circuit
breaker sized for the pump (20 amp max)
Allmetalttingsshouldbebonded
Mounting
Not in engine room or bilge areas, must be sealed away
from exhaust or fumes
Proper spacing allowed around unit
Attached to solid level platform with hold down clips
provided
Condensate drain routed aft and down hill to a sealed
sump (not bilge)
Blower rotated toward supply air grille
Electrical
The wiring diagram is located in the electrical box. If that
diagram is damaged or if you need a copy, please call
Dometic with the unit part number, serial number, and
wiring diagram number, all of which are located on the
unit data plate.
All butt connections on pumps wire tightly crimped and
heat shrunk
AC power source installed and grounded/bonded in
accordance with ABYC standards
Control wires connected to terminal strip with captive
fork or ring terminals
Circuitbreakerssizedaccordingtospecicationsonthe
data plate label
Digital display cable is connected at both ends
Pump Relay Panel (if used) has a dedicated circuit
breaker sized for the pump but not to exceed 20 amps
maximum.
Grilles and Ducting
Supply air grille mounted as high as possible
Return air grille mounted as low and as close to the a/c
unit as possible
Return air grille mounted away from bilge vapors or
exhaust fumes
Ducting is pulled taut, straight, smooth and properly
connected with no excess