5.2.1.2.3 Configuration of High Side Output Diagnostic Mode
The VC-EVCC provides the possibility to activate or deactivate the active off-state
diagnostics of the HSOUT0, HSOUT1 and HSOUT4. If the active off-state diagnostic is
configured as “On” the VC-EVCC will detect ShortToGnd and OpenLoad faults even if the
corresponding HSOUT is disabled.
The service structure is defined as 1 byte.
Bit Pos.
Description
Value
0
HSOUT0 Active off-state diagnostics
Off: 0 (default)
On: 1
1
HSOUT1 Active off-state diagnostics
Off: 0 (default)
On: 1
2
HSOUT4 Active off-state diagnostics
Off: 0 (default)
On: 1
Note
An update of the parameter requires a reboot of the VC-EVCC to be applicable.
The diagnostic service “Write Data By Identifier” is only available in the application
extended session.