The values listed in Table 1–1 relate to the system cabinet only. In-cabinet
storage will increase electrical requirements.
Table 1–1: Electrical Characteristics
Electrical
1
Hz Without VAXBI With VAXBI
AC power consumption
(max)
2.5 KVA 3.5 KVA
AC current (nom) 60 7.0 A (208 V) 9.7 A (208 V)
50 3.5 A (416 V)
3.8 A (380 V)
4.8 A (416 V)
5.3 A (380 V)
Voltage input 60 3-phase 208 V RMS
50 3-phase 380/416 V RMS
Frequency tolerance 47–63 Hz
Surge current 60 A
1
These values assume a base system with no optional disks or battery backup unit.
Table 1–2: Environmental Characteristics
Environmental
Heat dissipation (max) 5570 Btu/hr
Operating temperature TF/TK not in use 10
o
to 40
o
C (50
o
to 104
o
F)
1
TF/TK in use 15
o
to 32
o
C (59
o
to 90
o
F)
Operating humidity TF/TK not in use 10 to 90% relative humidity
TF/TK in use 20 to 80% relative humidity
Altitude Operating 0 to 2.4 km (0 to 8000 ft)
Nonoperational 0 to 9.1 km (0 to 30,000 ft)
1
Model 600 range: 15
o
to 32
o
C (59
o
to 90
o
F)
The VAX 6000 Series System 1–3