Technical data
2.1.7 Electrical Requirements
The power source should be adequate to handle the original system and
allow for system expansion. Digital recommends a dedicated circuit from
the power source to each system. Additional power equipment may be
required to avoid power disturbances.
Table 2–2 lists the electrical requirements for systems in a BA430/BA440
pedestal. Table 2–3 lists the power cords required.
Table 2–2: BA430/BA440 Enclosure Electrical Requirements
Nominal AC Voltage 101 Vac 120 Vac 220–240 Vac
Voltage range 90 to 110 Vac 104 to 128 Vac 176 to 264 Vac
Power source phase Single Single Single
Nominal frequency 50 to 60 Hz 50 to 60 Hz 50 to 60 Hz
Frequency range 47 to 63 Hz 47 to 63 Hz 47 to 63 Hz
Maximum steady state current
at nominal voltage
10.2 A 8.6 A 4.7 A
Maximum steady state current
at minimum voltage
12 A 11.1 A 6.82 A
Startup current (30 seconds) 13.7 A 11.5 A 6.3 A
Maximum inrush current 100 A 100 A 100 A
Maximum power consumption 1139 W 1139 W 1139 W
Table 2–3: Power Cords
Power Cord Countries
BN20A–2E United States, Japan, and Canada (17–00083–43 (120 V))
BN20B–2E United States, Japan, and Canada (17–00083–44 (240 V))
BN22C–2E Australia and New Zealand
BN22D–2E Central Europe, Austria, Belgium, Finland, France, West
Germany, Netherlands, Norway, Portugal, Spain, and Sweden
BN22E–2E United Kingdom and Ireland
BN22F–2E Switzerland
BN22H–2E Denmark
BN22J–2E Italy
BN22K–2E India and South Africa
BN22L–2E Israel
2–4 BA430/BA440 Enclosure Maintenance