Table 1–2 VAX 6000 Series System Characteristics
Physical cm (in)
Height 154 (60.5)
Width 78 (30.5)
Depth 76 (30.0)
Weight 341 kg (750 lbs)
Environmental
Heat dissipation (max) 5440 Btu/hr (5712 KJ/hr)
Operating temperature 10
o
to 40
o
C (50
o
to 104
o
F)
Operating humidity 10% to 90% relative humidity
Altitude Nonoperational 0 to 9.1 km (8000 to 30,000 ft)
Operating 0 to 2.4 km (0 to 8000 ft)
Cooling System
Type Pressurized, with air moving device
Air mover Dual backward curved blowers
Air source Filtered ambient air
Electrical
AC power consumption
(max)
1.4 kW
1
AC current (max) 60 Hz 8 A (208 V)
50 Hz 4 A (416 V), 4.5 A (380 V)
Voltage input 60 Hz 3-phase 208 V RMS
50 Hz 3-phase 380/416 V RMS
Frequency tolerance 47–63 Hz
Surge current 60 A
1
Not including single-phase power to disks or battery backup unit.