Installation guide

Console 3-21
3.10 Show Power Command
Example 3-6 Show Power Command
>>> show power
Cabinet: Main Regulator : A B C
-------------------------------------------------------------------------------
Primary Micro Firmware Rev : 2.0 2.0 2.0
Secondary Micro Firmware Rev : 2.0 2.0 2.0
Power Supply State : NORMAL NORMAL BBU MODE
AC Line Voltage (V RMS) : 113.71 114.35 115.93
DC Bulk Voltage (VDC) : 227.02 227.02 227.02
48V DC Bus Voltage (VDC) : 47.57 47.57 47.57
48V DC Bus Current (ADC) : 30.17 29.68 29.58
48V Battery Pack Voltage (VDC) : 50.85 50.72 47.91
24V Battery Pack Votlage (VDC) : 25.56 25.56 23.95
Battery Pack Charge Current (IDC) : 2.91 2.90 0
Ambient Temperature (Degree C) : 26.22 24.80 24.75
Elapsed Time (Hours) : 290.00 290.00 290.00
Remaining Battery Capacity (Minutes) : 8.00 8.00 8.00
Battery Cutoff Counter (Cycles) : 0 1.00 1.00
Battery Configuration : 4 Batteries 4 Batteries 4 Batteries
Heatsink Status : NORMAL NORMAL NORMAL
Battery Pack Status : CHARGING CHARGING DISCHG’G
Last UPS Test Status : PASSED PASSED TESTING
LDC POWER Status : 0
PIU Primary Status : 0
PIU Secondary Status : 0
The cabinet in Example 3-6 has three power regulators. If the cabinet has
fewer than three regulators, the appropriate column (A, B, or C) is left
blank. The bottom three lines of the output, showing PIU power status,
apply only to the main cabinet.
Table 3-17 lists the abbreviations used in four lines of the Show Power
command: Power Supply State, Heatsink Status, Battery Pack Status,
and Last UPS Test Status.
For more information:
VAX 7000 Console Reference Manual