User manual
SVA026 Netcom 2 User Manual ver5
70
STATUS mandatory
DESCRIPTION
"Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occur immediately. Setting this
object to -1 will abort the countdown. If the output
is already on at the time the countdown reaches 0,
then nothing will happen. Sets to this object
override the effect of any upsStartupAfterDelay
countdown or upsRebootWithDuration countdown in
progress. When read, upsStartupAfterDelay will return
the number of seconds until startup, or -1 if no
startup countdown is in effect. If the countdown
expires during a utility failure, the startup shall
not occur until the utility power is restored. On
some systems, if the agent is restarted while a
startup countdown is in effect, the countdown is
aborted."
::= { upsControl 3 }
upsRebootWithDuration OBJECT-TYPE
SYNTAX INTEGER -- UNITS seconds
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored."
::= { upsControl 4 }
upsAutoRestart OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a