"The indication of the capacity remaining in the UPS
batteries.
A value of batteryNormal indicates a normal battery
condition.
A value of batteryLow indicates the remaining battery run-
time
will not maintain the output load for an extended period of
time.
A value of batteryDepleted indicates that the UPS will be
unable
to sustain the present load when and if the utility power
is lost."
::= { upsBattery 1 }
upsSecondsOnBattery OBJECT-TYPE
SYNTAX NonNegativeInteger -- UNITS seconds
ACCESS read-only
STATUS mandatory
DESCRIPTION
"If the unit is on battery power, the elapsed time in
seconds
since the UPS last switched to battery power, or the time
since
the network management system was last restarted, whichever
is less.
Zero shall be returned if the unit is not on battery
power."
::= { upsBattery 2 }
upsEstimatedMinutesRemaining OBJECT-TYPE
SYNTAX PositiveInteger -- UNITS minutes
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An estimate of the time in minutes until the battery is
depleted
under the present load conditions if the utility power is
off and
remains off, or if it were to be lost and remain off."
::= { upsBattery 3 }
upsEstimatedChargeRemaining OBJECT-TYPE
SYNTAX INTEGER -- UNITS percent
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An estimate of the battery charge remaining expressed as a
percent of full charge."
::= { upsBattery 4 }
upsBatteryVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger -- UNITS 0.1 Volt DC
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the present battery voltage (0.1 Volt
DC)."