User manual
SVA026 Netcom 2 User Manual ver5
30
9. Input Out of Range, when the UPS input voltage deviates from the UPS’s
operating parameters a shut down message will be sent after the preset time limit
has been reached.
10. Overload, when the unit is overload and the preset timer has expired a shut down
message will be sent.
11. Temperature Out of Range, when the UPS experiences temperature that exceed
the operating standards and the timer has elapsed a shut down message will be
sent.
Each parameter has a time limit or percentage attached to it. If the parameter is reached
but does not remain for the duration of the time or percentage limit a shutdown will NOT
be initiated.
The Configure Shutdown Agents when selected.
Figure 7.10
The UPS/Shutdown setup can be accessed by selecting Configure Shutdown
Agents. Figure 7.10 is an example of the page. In this page the user can input up to 500
devices.
The user will input the devices IP address, name and time delay that is selectable
in minutes. The Agent IP Address is the IP address of the item that will be shut down
when the shut down message is sent. The computer/server must have a shut down agent
installed prior to testing the shut down.
After the user enters the devices that are going to be shut down by the Netcom a
test can be performed by selecting the test button (THIS WILL SHUT DOWN ALL
DEVICES ENTERED). The user can also download the shutdown entries to a CSV file.
This file can be modified and uploaded back into the device using the update feature on
the bottom left of the page.