7.9Shutdown/UPSShutdownSetupPage
Figure 7.9
Figure 7.9 is an example of the UPS/Shutdown Configuration page. In this page the
user can select the UPS activity that will trigger a shut down message, by enabling a
parameter the user can send a shut down on;
1. Battery Capacity percentage, when the UPS detects the percentage of battery
remaining a shutdown will be initiated after the time limit has elapsed.
2. Estimated Runtime, when the UPS detects the estimated run time has been
reached a shut down message will be initiated after the time limit has elapsed.
3. On Battery, when the UPS is on batteries for the preset duration a shutdown
message will be sent after the preset time has elapsed.
4. Low Battery Alarm, when the low battery alarm has been detected by the UPS a
shut down message will be sent after the preset time limit has elapsed.
5. Battery Discharge, when the unit is discharging the battery string a shut down
message will be sent after the present time has elapsed
6. Battery Failure, when the UPS has detected a battery failure a shut down message
will be sent.
7. Bypass ON Auto, when the UPS is transferred to bypass either manually or
automatically a shut down message will be sent after the preset time limit has
elapsed.
8. Output Out of Range, when the UPS Output voltage deviates from the UPS’s
operating parameters a shut down message will be sent after the preset time limit
has elapsed.