Installation guide
1.5 AC Power Cable and Connectors
The AC power cable is 4.6 m (15 ft) in length. It consists of
three-phase leads (X, Y, and Z) plus neutral (W/N) and ground
(G). AC power connectors for 60 Hz and 50 Hz systems are
shown below. See Section 6.3.
CAUTION: Neutral and ground lines must both be connected from
the bulk three-phase power to complete the Wye configuration.
Otherwise, power components may be damaged. Power must not
be connected to the site source until the power checks of Chapter 6
are performed.
Figure 1–6: AC Power Connectors
RECEPTACLE
# 2510
L21-20R
12-11210-11
PLUG
HUBBELL # 2511
NEMA # L21-20P
DEC # 12-11209-00
208 V
3-PHASE Y
380 V OR 416 V
3-PHASE Y
PLUG
RECEPTACLE
Y
Z
N
X
X
Y
N
Z
# 516R6W
12-14378-04
HUBBELL # 516P6W
DEC # 12-14379-04
G
Y
X
W
Z
Z
W
X
Y
G
G
G
1–12 VAX 6000 Series Installation Guide