Installation guide

Console Commands 3-41
3.27 Show Power
The show power command gives the power status of the system.
Example 3-27 Show Power Command
>>> show power
Cabinet: Main Regulator : A B C
-------------------------------------------------------------------------------
Primary Micro Firmware Rev : 2.0 2.0 2.0
Secondary Micro Firmware Rev : 2.0 2.0 2.0
Power Supply State : NORMAL NORMAL BBU MODE
AC Line Voltage (V RMS) : 113.71 114.35 115.93
DC Bulk Voltage (VDC) : 227.02 227.02 227.02
48V DC Bus Voltage (VDC) : 47.57 47.57 47.57
48V DC Bus Current (ADC) : 30.17 29.68 29.58
48V Battery Pack Voltage (VDC) : 50.85 50.72 47.91
24V Battery Pack Voltage (VDC) : 25.56 25.56 23.95
Battery Pack Charge Current (IDC) : 2.91 2.90 0
Ambient Temperature (Degree C) : 26.22 24.80 24.75
Elapsed Time (Hours) : 290.00 290.00 290.00
Remaining Battery Capacity (Minutes) : 8.00 8.00 8.00
Battery Cutoff Counter (Cycles) : 0 1.00 1.00
Battery Configuration : 4 Batteries 4 Batteries 4 Batteries
Heatsink Status : NORMAL NORMAL NORMAL
Battery Pack Status : CHARGING CHARGING DISCHG’G
Last UPS Test Status : PASSED PASSED TESTING
LDC POWER Status : 0
PIU Primary Status : 0
PIU Secondary Status : 0