User`s manual

VARILITE - VL1100CD ERS LUMINAIRE USERS MANUAL
28 15 February 2011 02.9665.0001 0
Control Channel Functions
Control channel functions allow special actions such as reset, lamp on/off and partial recalibration.
These must be executed with zero time transition or with timing disabled. Discrete values must be
used; not manual controls such as faders or encoders (see chart below for values).
Reset - resets all luminaire mechanisms.
Lamp On or Lamp Off - switches lamp on or off.
Partial Recalibration - resets only the target mechanism (color, gobo, zoom, etc.) without affecting
others.
* For arc models, the dimmer will close during each recalibration action.
To use control channel functions:
Step 1. Select an action to be sent.
Step 2. Set control channel value for desired action (for example, 84 for reset). Hold value for 3
seconds.
Note: A numerical keypad is required for sending values. An encoder or fader does not allow for a
quick value change, which is required to effect the control functions.
Step 3. Set control channel value to zero. (This must occur without any scaling values. Action will
be voided if other values are detected between action value and zero.)
Table 3-3: Control Channel Functions
Control
Channel
Function
Control Channel Value
% Value
DMX Value
For 3 Secs
or Greater
After
3 Secs
Luminaire Reset 32-33 81-87 0
Lamp Off 65-67 165-171 0
Lamp On 98-100 249-255 0
Partial Recalibration of:
- Blue/Amber/Magenta/Diffuser * 40 100-104 0
- Rotating Gobo/Index * 45 113-117 0
- Edge/Zoom * 50 126-130 0
- Beam Size Iris/Shutter * 55 138-142 0