8315 TGI Software Description
Varec, Inc. 39
Application
The SCALER point allows you to perform simple math functions such as conversion of units. The
SCALER point takes the value from user-specified database references, multiplies each by a
constant and adds the three product terms. A constant K may also be factored in. The SCALER
point works in conjunction with parameters that are in floating point format.
4.4.10 System Information (SYS)
The System Information Point lists the hardware and software specifications of the
system. Other information includes the hardware version and any connected devices.
Parameters
The database parameters used by the SYS point are listed and described below:
PntStatus Byte value indicating status of point Values are:
0: No error
15: Invalid Type for PntRef
16 Invalid Number for PntRef
17 Invalid Param for PntRef
19: PntRef point does not exist
25: PntRef is not defined
Elapse Time the SCALER point last executed.
PntCheckSum CRC-16 Checksum of point's static Configuration Parameters
Dynamic Parameters Function
Configuration Parameters Function
RTUTag RTUTag can contain 15 bytes of data and can include any printable ASCII
character.
DBFile The database file name. DBFile is the name of the RCF database
configuration file
DBVer The database version.
PntEnable Disable/Enable execution of points. Default is Enable.
Dynamic Parameters Function
UnitAddr The Unit Address (SW1) for the 8300 series Tank Gate Interface.
DBPnts The number of database points defined.
DBSize The size of the database in bytes.
DBChangeTime The time of last database modification.
SysVer The firmware version.
SysCheckSum The system checksum.
HardVer The PCB hardware version.
PSDVer The programmable logic version.
PntCheckSum CRC-16 Checksum for point's static Configuration Parameters.