Technical information
5
Typical Tank calculations
Setup preset Installation example Sensors measured/
calculated values
required parameters
Direct level measurement
Level only
L00-NRF590-14-00-08-yy-002
• Level sensor • level • Tank Ref Height
Level + Temperature
L00-NRF590-14-00-08-yy-003
• Level sensor
• Temperature sensor
(RTD or
HART device;
optionally with bottm
water probe)
• level
• temperature
Hybrid Tank Measuring System (HTMS)
HTMS + P1
L00-NRF590-14-00-08-yy-004
• Level sensor
• Pressure sensor
(P1, bottom)
• level
• density of the measured
medium (calculated)
•Tank Ref Height
• P1 Position
•Min HTMS
(minimum level at which HTMS
measurement is possible; should be
slightly above the position of the P1
sensor)
•local gravity
• vapour density
• air density
• P3 Position (only for the "HTMS +
P1,3" mode)
HTMS + P1,3
!
Note!
This mode should be
used in non-
atmospheric tanks (e.g.
pressurised tanks)
L00-NRF590-14-00-08-yy-005
• Level sensor
• Pressure sensor
(P1, bottom)
• Pressure sensor
(P3, top)
Micropilot
Tank Side
Monitor
Tank Ref Height
Prothermo
Micropilot
Tank Side
Monitor
P1
Tank Side
Monitor
Micropilot
Tank Ref Height
P1 Position
P1
P3
Micropilot
Tank Side
Monitor
P3 Position