Technical information

11
Technical data of the non-IS
inputs and outputs
Analogue 4...20 mA input (option, s. pos. 20 of the product structure)
Analogue 4...20 mA outputs
Discrete inputs/outputs A and B
The Tank Side Monitor can be equipped with 1 or 2 discrete I/O modules.
Available types: see position 50 and 60 of Product Structure or chapter "Accessories".
Discrete output C (for V1 protocol)
Internal load (to ground) 110
Measuring range 0 ... 26 mA
Accuracy ±15 µA (after linearisation and calibration)
Output current 3 ... 24 mA
Output voltage U = 24 V - I
LOAD
400
Output load max. 500
Accuracy ±15 µA (after linearisation and calibration)
HART options
1)
1) The second analogue output (available for V1, WM550 and GPE) has no HART option.
Slave, address # 0:
4 ... 20 mA active
Slave, address #1 - #15:
fixed current (user selectable)
•Master:
max. current ( 24 mA) selectable by user;
typically 6 HART instruments (each 4 mA) can be connected
2)
2) Start-up current of the HART instruments has to be taken into account
Load voltage 3 ... 100 V
Load current max. 500 mA
Type of contact mechanical latching relay
Isolation voltage 1500 V
Approvals UL, CSA