Specifications
50
Reference Manual
00809-0100-2460, Rev AA
Section 4: Configuration
November 2014
Configuration
Step 3. Tank Database Configuration
1. Configure the Tank Database of the 2460 System Hub.
The 2460 Tank Database ensures that the 2460 System Hub requests information from all the
connected field devices. It is very important that the Tank Database of the 2460 System Hub is
properly configured to allow communication between the Rosemount 2460 System Hub, the
2410 Tank Hub, and field devices such as the Rosemount 5900S Radar Level Gauge, the
Rosemount 2240S Multi-Input Temperature Transmitter, pressure transmitters, and other field
devices supported by the 2460.
Note!
Once all devices and tanks are installed and configured, the position of a device in the Tank
Database may not be changed, since this will result in corrupt mapping of tank to Tank Database
position.
To configure the 2460 Tank Database:
a. Find a free tank position (2460 Tank 1, 2, 3...) for the device to be configured.
b. Choose the appropriate Source device.
For a Rosemount Tank Gauging system this is typically a Rosemount 2410 Tank Hub.
The 2460 System Hub also supports many other Rosemount Tank Gauging device types
as well. See Table 4-3 on page 53 for more information.