Specifications

47
Reference Manual
00809-0100-2460, Rev AA
Section 4: Configuration
November 2014
Configuration
How to change the Modbus address of the 2460 System Hub
a. In the 2460 Communication window click the Change Address on Device button to
open the Change Address window:
b. Enter the Device ID and the new Modbus address. For the 2460 System Hub address
range 201- 299 is recommended.
When changing the device address, the Device ID is used as a unique identifier of the
device. The Device ID can be found on a label mounted on the device.
Tip! If there is no other device connected that uses the same address as the current
device, you can find the Device ID by typing the current address into the Address field in
the 2460 System Hub Communication window and clicking the Verify Communication
button.
c. Click the OK button to confirm the settings and close the Change Address window.
d. In the 2460 System Hub Communication window click the Verify Communication
button to check if communication is established between the TankMaster work station
and the 2460 System Hub. The Device ID will appear when TankMaster finds the 2460.