Modbus Implementation Tank Gauge Transmitter
58 Installation and Operations Manual
7 Bit Field CmdsBit Usage
0 CANCEL ALT
1 CLR LOCAL MODS
2 RESTART
3 SAVE TO EE
4 RESERVED
5 CALIB LEVEL
6 ENC BATT OFF
7 QUICK SETUP
8.15 RESERVED
8 Reserved
9 Code A/D Noise Reject: Type
0 - 60Hz
1 - 50 Hz
10 Scaled Crit Low Level Setpoint
11 Scaled Adv Low Level Setpoint
12 Scaled Adv High Level Setpoint
13 Scaled Crit High Level Setpoint
14 Scaled Level Deadband
15 Scaled Crit Low Temp Setpoint
16 Scaled Adv Low Temp Setpoint
17 Scaled Adv High Temp Setpoint
18 Scaled Crit High Temp Setpoint
19 Scaled Temp Deadband
20 Code Level Units
0 - METERS
1 - FEET
2 - FT-IN-16TH
21 Code Temp Units
0 - C
1 - F
2 - K
22 Code Level Type
1 - FORWARD
2 - REVERSE
23 Code Temp Type
0 - NONE
1 - COPPER RTD
2 - PLATINUM RTD
24 Scaled Manual Temperature
25 Code Max Integer Value
26 Code Damping Value
27 Scaled Calibration Level
Register Number Type Description