Instruction manual

Varec, Inc. 59
7532 Radar Tank Gauge
Note
The offset should not be determined and entered within the close range of the
antenna (confirm the definition of the safety distance) or immediately in the
range of the tank bottom, because within these ranges interferences of the
radar signal may occur.
The dip table can be printed out using FieldCare. Before doing this, FieldCare
must be reconnected to the device in order to update the values within
FieldCare.
Make your inputs into the dip table in semi-automatic mode. We advise you to
leave “auto correction” (031) activated (“on”) while you enter your inputs.
Caution! After entering one or more points into the dip table, make sure that the
dip table is activated and left in the “table on” dip table mode.
Function “dip table state” (037)
This function displays the dip table status.
Display:
table on
table off
Table on
Indicates whether the dip table is active.
Table off
Indicates whether the dip table is not active.
Function “dip table mode” (033)
The dip table can be switched on or off using this function.
Selection:
Manual
Semi-automatic
Table on
Table off
Clear table
View