7532 Radar Tank Gauge
Function “empty calibr.” (005)
This function is used to enter the distance from the flange (reference point of the
measurement) to the minimum level (= zero).
Figure 7-3: Distance from the Flange (Reference Point of the Measurement)
Caution! For dish bottoms or conical outlets, the zero point should be no lower
than the point at which the radar beam hits the bottom of the tank.
Function “full calibr.” (006)
This function is used to enter the distance from the minimum level to the maximum level
(= span).