Commissioning
46 Installation and Operations Manual
7.4 Basic Setup with the VU331
Function “measured value” (000)
This function displays the current measured value in the selected unit
(see “customer unit” (042)) function). The number of digits after decimal point can be
selected in the “no.of decimals” (095) function. The length of the bar graph corresponds
to the percentile value of the present measured value with regard to the span.
Function group “basic setup” (00)
Function “tank shape” (002)
This function is used to select the tank shape.
Selection:
• dome ceiling
• horizontal cyl
• bypass
• stilling well (factory settings for 7532 RTG)
• flat ceiling (Typical ceiling of storage tanks: a slight slope of only a few degrees can
be neglected.)
• sphere