Instruction manual
Varec, Inc. 45
7532 Radar Tank Gauge
Caution! To successfully commission a precise measurement to the nearest mm,
it is important you carry out a history reset on first installation after mechanical
installation and after the basic setup of the device (see page 53). Only after a
history reset the mounting calibration is carried out. Enter the measurement offset
as the first point in the dip table for the mounting calibration. When a value is
dipped at a later date, make a second entry into the dip table, using the semi-
automatic mode. This way, you can easily carry out a linear correction of the
measurement.
When configuring the function in “basic setup” (00), please take into account the
following notes:
• Select the functions as described in the “Quick Operation Guide” on page 31.
• Some functions can only be used depending on the parameterization of the device.
For example, the pipe diameter of a stilling well can only be entered if “stilling well”
was selected beforehand in the “tank shape” (002) function.
• Certain functions (e.g. starting an interference echo mapping (053)) prompt you to
confirm your data entries. Press to select “YES” and press to confirm.
The function is now started.
• If you do not press a key during a configurable time period (» function group
“display” (09)), an automatic return is made to the home position (measured value
display).
Note
• The device continues to measure while data entry is in progress, i.e. the current
measured values are output via the signal outputs in the normal way.
• If the envelope curve mode is active on the display, the measured values are
updated in a slower cycle time. Thus, it is advisable to leave the envelope curve
mode after the measuring point has been optimized.
• If the power supply fails, all preset and parameterized values remain safely
stored in the EEPROM.
• All functions are described in detail, as is the overview of the operating menu
itself, in the manual “IOM117 - Description of Instrument Functions”.
• The default values of the parameters are typed in boldface.
+
-