6.2.3.1 Software reliability
The software used in the 7500 series RTG, fulfills the requirements of OIML R85.
This particularly includes:
cyclical test of data consistency
non-volatile memory
segmented data storage
The 7500 series RTGs continuously monitor the compliance with accuracy requirements
for custody transfer measurements according to OIML R85. If the accuracy cannot be
maintained, a specific alarm is generated on the local display and via the digital
communication (see »Display symbols« on page 34).
6.3 Local Operation
6.3.1 Locking configuration mode
The 7532 RTG can be protected in two ways against unauthorized changing of the device
data, numerical values, or factory settings:
Function “unlock parameter” (0A4):
A value <> 100 (e.g. 99) must be entered in “unlock parameter” (0A4) in the
“diagnostics” (0A) function group. The lock is shown on the display by the symbol
and can be released again either via the display or by communication.
Hardware lock:
The instrument is locked by pressing the keys at the same time.
The lock is shown on the display by the symbol and can only be unlocked again via
the display by pressing the keys at the same time again.
It is not possible to unlock the hardware by communication. All parameters can be
displayed even if the instrument is locked.
Table 6-6: Hardware Lock
E
and
-
and
+
E
and
-
and
+
press simultaneously
The LOCK_SYMBOL appears on the LCD
E
+
E
and
-
and
+