Installation manual
www.fmiproducts.com
113195-01N 7
a.  walls and ceilings exposed to the out-
side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6 x 10
-11 
kg per pa-sec-m
2
) or 
less with openings gasketed or sealed 
and
b.  weather stripping has been added on 
openable windows and doors and
c.  caulking  or  sealants  are  applied  to 
areas  such  as  joints  around  window 
and door frames, between sole plates 
and oors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical and gas lines 
and at other openings.
If your home meets all of the three criteria 
above, you must provide additional fresh 
air.  See  Ventilation Air From Outdoors, 
page 8.
If your home does not meet all of the three 
criteria  above,  proceed  to  Determining 
Fresh-Air Flow for Heater Location.
Conned and Unconned Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 denes a conned space as a space 
whose volume  is  less than  50  cubic feet per 
1,000 Btu per hour (4.8 m
3
 per kw) of the ag-
gregate input rating of all appliances installed in 
that space and an unconned space as a space 
whose volume is not less than 50 cubic feet per 
1,000 Btu per hour (4.8 m
3
 per kw) of the ag-
gregate input rating of all appliances installed in 
that space. Rooms communicating directly with 
the space in which the appliances are installed*, 
through openings not furnished with doors, are 
considered a part of the unconned space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Conned or 
Unconned Space
Use this work sheet to determine if you have 
a conned or unconned space.
Space: Includes the room in which you will install 
replace  plus  any  adjoining  rooms  with  door-
less passageways or ventilation grills between 
the rooms.
1.  Determine the volume of the space (length 
x width x height).
  Length x Width x Height =__________cu. ft. 
(volume of space)
AIR FOR COMBUSTION AND VENTILATION
Continued
  Example: Space size 22 ft. (length) x 18 ft. 
(width) x 8 ft. (ceiling height) = 3168 cu. ft. 
(volume of space)
  If additional ventilation to adjoining room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
   ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
  Example: 3168 cu. ft. (volume of space) x 20 
=  63,360  (maximum  Btu/Hr  the  space  can 
support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
  Vent-free replace   __________ Btu/Hr
  Gas water heater*   __________ Btu/Hr
  Gas furnace   __________ Btu/Hr
  Vented gas heater   __________ Btu/Hr
  Gas replace logs   __________ Btu/Hr
  Other gas appliances* + _________ Btu/Hr
 Tota  = _________ Btu/Hr
  * Do not include direct-vent gas appliances. 
Direct-vent draws  combustion  air  from the 
outdoors and vents to the outdoors.
  Example:
  Gas water heater   __________ Btu/Hr
  Vent-free replace  + _________ Btu/Hr
 Total  = _________ Btu/Hr
4.  Compare the maximum Btu/Hr the space 
can support with the actual amount of Btu/
Hr used.
   _______
Btu/Hr (maximum the space can 
support)
   _______
Btu/Hr (actual amount of Btu/Hr 
used)
  Example:  63,360  Btu/Hr  (maximum  the 
space can support)
    73,000 Btu/Hr (actual amount of 
Btu/Hr used)
The space in the above example is a conned 
space because the actual Btu/Hr used is more 
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air. Your 
options are as follows:
A.  Rework  worksheet,  adding  the  space  of 
an adjoining room. If the extra space pro-
vides  an  unconned  space,  remove  door 
to adjoining room or add ventilation grills 
between rooms. See Ventilation Air From 
Inside Building, page 8.
B. Vent room directly to the outdoors. See 
Ventilation Air From Outdoors, page 8.
C.  Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
  40,000
  33,000
  73,000










