default, unplug the device, press and hold both buttons in and
plug it in while holding the buttons down. After a reset the load
profile will be Default, the learn levels will be 100%, the load will
be off, and other settings will be at factory default.
Note: If the Station Load was changed to RELAY* this Process
will change it back to DIM. Make sure it is back on-line with the
Main Controller before testing button or relay load operation.
*CAUTION: The station is shipped in “DIMMING MODE”. To
change the default mode to RELAY change the Power Profile to
Relay in Software. The Relay Mode change will not take place
until the system is programmed and the RF station is on line. A
motor should not be connected to the AccentPoint Dimmer
station, instead use the AccentPoint Relay station.
Diagnostic Information
A red Status LED is located on top of the device. The Status
LED blinks evenly or flashes 2, 3, or 4 times followed by a pause
to indicate status information.
Off: The station is not powered. A line voltage connection has
not been made or the line feed breaker is off.
One Even blink: Station is operating correctly and is configured.
Two blinks: Station should be reset. See Reset above.
Three blinks: Station is not added to the network. Verify that its
serial number has been programmed into the Main Controller
and that the station is within 100 Feet of the RFE1000.
Four blinks: Lamp Dimmer problem. Please contact the factory.
FCC Compliance Information:
FCC ID: PII-AP2RL
IC: 3505A-AP2RL
The enclosed device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device
must accept any interference received, including interference
that may cause undesired operation.
NOTE: This equipment has been tested and found to comply
with the limits for a Class B digital device, pursuant to Part 15 of
the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential
installation. This equipment generates uses and can radiate
radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference
by one or more of the following measures:
-- Reorient or relocate the receiving antenna.
-- Increase the separation between the equipment and receiver.
-- Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
-- Consult the dealer or an experienced radio/TV technician for
help.
Changes or modifications to this product not expressly approved
by Vantage Controls could void the user’s authority to operate
this product.