Owner`s manual

TSR-1 Remote Control
TruSine 4.5 kW Inverter Page 13 Owner’s Manual
the charger. Changes to other system functions or setpoints will not go into effect until the system is reset.
Reset the system by turning the System ON/OFF Switch, located on the front of the inverter, OFF for 5 seconds
and then back ON. When changing setpoint values you must leave that screen before resetting the system.
The system also can be reset via the TSR-2. When changing inverter functions, disable/enable the inverter to
reset the inverter. When changing charger functions, disable/enable the charger to reset the charger. Reset
both if in doubt.
Password
Acceptance of factory setpoints or adustments to setpoints should be made only by qualified personnel. If
certain setpoints are incorrect then system performance degradation or external equipment damage could
occur; i.e. battery damage due to improper charging, etc. The most sensitive system adjustments are located in
the Advanced Control Menu which is password protected. The password for gaining access to the Advanced
Control Menu consists of pressing the four Control Buttons in the following sequence: upper left, lower right,
lower left, upper right.
3.4 Menu Map
Initial Display (Push any button to enter main menu.)
TSR-2
A88769-A
MAIN MENU:
Ref.
Step Display Function Action
1 BSCONTROL Selects the BASIC CONTROL submenu Go to Step 10
2 MONITOR Selects the MONITOR display submenu Go to Step 20
3 ALARMS Selects the ALARMS display submenu Go to Step 100
4 Down Arrow Scrolls down in the menu Go to Step 5
5 GENERAL INFO Selects the GENERAL INFO display submenu Go to Step 50
6 ADV CONTROL Selects the ADVANCED CONTROL submenus Go to Step 60
7 Up Arrow Scrolls up in the menu Go to Step 1
BASIC CONTROL Menu:
10 Inverter Allows inverter to operate automatically Controls inverter
ENABLED disabled (ENABLED) or turns inverter OFF (DISABLED).
11 Load Demand Allows Load Demand to operate automatically Controls inverter
ENABLED disabled or turns Load Demand OFF (DISABLED).
12 Enter Load Dmd Selects the size of the AC load at which the Controls inverter
+ XX Watts - inverter goes into Load Demand (asleep)
13 Exit Load Dmd Selects the size of the AC load at which the Controls inverter
+ XX Watts - inverter turns fully ON (wakes up)
14 Charger Allows charger to operate automatically Controls Charger
ENABLED disabled or turns the charger OFF (DISABLED)
15 Equalize Cycle Allows Equalize Cycle to operate automatically Controls Charger
ENABLED disabled or turns the Equalize Cycle OFF (DISABLED)
16 APM Limit Sets Automatic Power Management Amps Controls Charger
+ XX Amps AC -