AC Operating Ratings
AC Operating Voltage (Utility Interactive) 211.8 to 264 Vrms
AC Operating Voltage (Stand-alone) 211.8 to 264 Vrms
AC Maximum Output Current 18.75 Arms
AC Maximum Output Fault Current
(Measured when L1 is shorted to L2.)
56.25 Arms
AC Maximum Input Current
(From grid when charging)
30 amp APM rating
18.75 Arms for Inverter/Charger
AC Operating Frequency Range 59.75 Hz to 60.25 Hz
Output Neutral to Ground Not Bonded
(Good AC wiring practice dictates
that bonding between neutral and
ground should take place in the AC
distribution panel only.)
Charger
Maximum Charge Current Supported 100 ADC
Types of Charge supported Bulk, Absorption, Float, and Equalize
Types of Batteries Supported Lead Acid: Flooded-Cell, GEL, or
AGM
DC Input Voltage (Inverter Input)
DC Input Voltage Range 21.0 to 31.0 VDC - RE24-4500
41.0 to 62.0 VDC - RE48-4500
DC Input Current at 24VDC (Inverter Input)
Inverter OFF 1 ma
Inverter in Load Demand (No AC load) 0.5 amps
Inverter ON with no AC load 2.0 amps
Inverter with full load at 22VDC (4500W @ 25
°
)
225 amps
System
Generator Start & Low Battery Warning Control Relays
Rating
2 Amps 120 VAC / 2 Amps up to
100VDC
Efficiency 80% Nominal (at 22VDC for 24V
System, full load, at 44VDC for 48V
System, full load)
90% peak
Ambient Operating Temperature -40° to +40°C (-40 to +104°F) (to
+60°C (+140°F) with de-rated
output)
Cooling Air Thermostatically Controlled Fan
Enclosure Powder-Coated Aluminum / Wall
Mounting
Dimensions 29½ H x 20½ W x 9¼ D
Unit Weight 95 pounds