Installation manual
System Operation Description
5-7
Copyright
2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
sufficiently, as shown in the chart below, the inverter will
shutdown.
254 Vrms
330 Vrms
420 Vrms
Indefinitely
10
Seconds
.033
Second
.01667
Second
211 Vrms
120 Vrms
60 Vrms
10
Seconds
.033
Second
.01667
Second
Low Battery Shutdown
There are two cases that will trigger a low battery shutdown. In
one case, there is no AC present to charge the batteries and in
the other, charging is disabled. When a low battery shutdown
occurs the inverter will not restart until the battery voltage rises
above the Battery shutdown voltage.
The assumption is that there is another source for battery
charging. This avoids cycling the inverter Off and On and
possibly harming the batteries when they are discharged.
Chart 5-1: Current Regulation (Brownout) Mode Shutdown Time