Installation manual

RE Owners Manual
4-10
Copyright
2001 Phone: (614) 771-271 RE-4500
Vanner Inc. FAX: 614-771-4904 Installation Manual
4282 Reynolds Dr. www.vanner.com Rev 10d
Hilliard Ohio 43026 RE Owners_Manual_Rev10d D99988
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
(25) Option Connector
This connector is supplied to support the Generator Option in
the Vanner AC Control Module (RE-ACM) please review the
manual supplied with the RE-ACM unit for more information.
(26) AC Output Terminations
Terminations for the Load to be connected to the RE-4500 are
connected to the proper terminals: L1 is Phase 1, N is Neutral,
and L2 is Phase 2 of a split phase system.
Warning
Check Polarity Carefully! Improper wiring of these terminations can
result in loss of life, damage to this system, damage to connected
loads, and voiding of Warranty.
Check your terminations carefully!
(27) AC Input Terminations
Terminations for the Utility to be connected to the RE-4500 are
connected to the proper terminals: L1 is Phase 1, N is Neutral,
L2 is Phase 2, and GND is Chassis Ground for the split phase
Grid connection.
Warning
Check Polarity Carefully! Improper wiring of these terminations can
result in loss of life, damage to this system, damage to connected
loads, and voiding of Warranty.
Check your terminations carefully!
Note
The Output Neutral is not bonded to Ground at the Inverter.
(28) Chassis Ground Bonding Lug
The Chassis Ground Bonding Lug is used to create a tie point
for connecting the Chassis of the RE-4500 to ground.
(29) Cooling Fan
The cooling air exhaust fan is located on the Bottom of the
inverter. Air is brought in through the front cooling slots as
well as the rear plenum and exhausted at the bottom of the