(18) Relay C Contacts – Gen. Start
These terminals are available to the user from the RE-4500 and
can be used for several programmable functions. These
functions are listed in Table 4-3: Relay Configurations for
Relay C. The Factory Setting function for this set of contacts is
Generator Start
. These three Terminals are designated as
Normally Open, Common, and Normally Closed.
Function Configuration Comments
Generator Start Form C Factory Default
(19) Relay D Contacts
These terminals are available to the user from the RE-4500 and
can be used for several programmable functions. These
functions are listed in Table 4-4: Relay Configurations for
Relay D. There is no Factory Setting function for this set of
contacts. These three Terminals are designated as Normally
Open, Common, and Normally Closed.
Function Configuration Comments
Not assigned Form C
(20) Control Relay Ground Terminal
This terminal supplies 24VDC Ground for use in powering
relays in the RE24-4500 Inverter system.
(21) Control Relay Auxiliary VDC Output Terminal
In the RE24-4500, this terminal supplies 24VDC (current
limited to 1 Amp) for use in wetting 24VDC relays contacts. In
the RE48-4500 this terminal provides 48VDC for use in
wetting 48VDC contacts.
Table 4-3: Relay Configurations for Relay C
Table 4-4: Relay Configurations for Relay D