(9) Battery LED
Off Should only happen when the RE-4500 is turned off.
Green The Battery Voltage is Good. (Between 22 and 31 VDC /
Factory settings).
Orange The Battery Voltage is above the Low Battery Shutdown value
(Factory setting 21 VDC), but it is below the Low Battery
Warning value (Factory setting / 22 VDC). The Low Battery
Warning relay is ON.
Red The RE-4500 has shutdown because either the Battery Voltage
is above the High Battery Shutdown value (Factory setting 31
VDC) or is below the Low Battery Shutdown value (Factory
setting / 21 VDC). If the latter case is true, then the Low
Battery Warning relay is ON or the battery is “dead.”
(10) Utility LED
Off The Inverter is OFF.
Green The RE-4500 is attached to the Grid. The Grid frequency and
voltage are within preset limits, and the transfer relay is engaged.
The inverter is in either BYPASS, CHARGING, or GRID-
INTERACTIVE modes.
Orange The RE-4500 is waiting to phase-lock. The Grid frequency and
voltage are both within preset limits. When the AC good timeout
has expired (Factory setting 90 S) then the bypass relay will
engage and the LED will turn green.
Red An unacceptable grid condition is present. The voltage, the
frequency, or both are outside acceptable limits.