(6) Charging LED
Off The RE-4500 is not CHARGING or in a GRID-INTERACTIVE
mode or they both have been turned OFF.
Green The RE-4500 is CHARGING or in a GRID-INTERACTIVE
mode.
Orange Unused.
Red Unused.
(7) Temperature LED
Off This should never happen when the inverter is on. The LED is
burned-out.
Green
The RE-4500’s internal temperature is between -40 and +35
°
C.
Orange
The RE-4500 is operating at a temperature above +35
°
C. The fan
is on, its internal temperature is above 35
°
C, or the “Brick” or
Small Inverter temperature is above 75
°
C.
Red The RE-4500 has shutdown due to over temperature. The fan is
FULLY on, its internal temperature is above 60
°
C, or the “Brick”
or the Small Inverter temperature is above 90
°
C or the Large
Inverter Transformer temperature is above 75
°
C.
(8) Generator LED
Off The Generator Start option is OFF or the relay has NOT been
engaged.
Green The RE-4500 has engaged the Generator Start Relay, Grid AC
is present, and CHARGING is underway.
Orange The RE-4500 is trying to Charge, but a good Grid voltage is
not present. The relay is ON, but will go OFF after 90 S
(Factory setting).
Red The RE-4500 is trying to Charge, but a good Grid voltage is
not present. The relay is OFF.