OPERATING INSTRUCTIONS For TRI-PHASE™ True Three-Phase Transformer Turns-Ratio Tester Vanguard Instruments Co., Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: 909-923-9390 FAX: 909-923-9391 . October 2008 REV.
TRI-PHASE OPERATING™ INSTRUCTIONS SAFETY WARNINGS AND CAUTIONS Only trained operators shall use this device. All transformers under test shall be off line and fully isolated. Always ground the TRI-PHASE™ to a substation ground before connecting the test cables to a transformer Do Not Modify Test Equipment Because of the risk of introducing unknown hazards, do not install substitute parts or perform any unauthorized modifications to any TRI-PHASE™ test device.
TRI-PHASE OPERATING™ INSTRUCTIONS Table of Contents 1.0 Introduction ...........................................................................................................................10 1.1 Applicability.......................................................................................................................10 2.0 General Description...............................................................................................................10 3.0 Functional Description .............
TRI-PHASE OPERATING™ INSTRUCTIONS 13.17 Transformer Name Plate Voltage Menu For Another Test................................................48 13.18 Test Record Not Saved Menu ............................................................................................49 14.0 Dyn1 Transformer Test Procedure ........................................................................................50 14.1 Delta-To-Wye (Dyn) Transformer Test Column Format Printout.....................................53 14.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.14 Typical Three Phase Dyn1 Test Plan Printout .................................................................104 17.15 Erase A Test Plan Procedure ............................................................................................105 17.16 Erase Test Plan Menu.......................................................................................................106 17.17 Erase Test Plan Status Display...........................................................
TRI-PHASE OPERATING™ INSTRUCTIONS List of Tables Table 1.0 Table 2.0 Table 3.0 Table 4.0 Table 5.0 Table 6.0 Table 7.0 Table 8.0 Table 9.0 Table 10.0 Table 11.0 Table 12.0 Table 13.0 Table 14.0 Table 15.0 Table 16.0 Table 17.0 Table 18.0 Table 19.0 Table 20.0 Table 21.0 Table 22.0 Table 23.0 TRI-PHASE™ Turns-Ratio Meter Specifications .........................................................13 Supplied Cable Set ..............................................................................................
TRI-PHASE OPERATING™ INSTRUCTIONS Figure 1.0 Figure 2.0 Figure 3.0 Figure 4.0 Figure 5.0 Figure 6.0 Figure 7.0 Figure 8.0 Figure 9.0 Figure 10.0 Figure 11.0 Figure 12.0 Figure 13.0 Figure 14.0 Figure 15.0 Figure 16.0 Figure 17.0 Figure 18.0 Figure 19.0 Figure 20.0 Figure 21.0 Figure 22.0 Figure 23.0 Figure 24.0 Figure 25.0 Figure 26.0 Figure 27.0 Figure 28.0 Figure 29.0 Figure 30.0 Figure 31.0 Figure 32.0 Figure 33.0 Figure 34.0 Figure 35.0 Figure 36.0 Figure 37.0 Figure 38.0 Figure 39.0 Figure 40.
TRI-PHASE OPERATING™ INSTRUCTIONS Figure 52.0 Figure 53.0 Figure 54.0 Figure 55.0 Figure 56.0 Figure 57.0 Figure 58.0 Figure 59.0 Figure 60.0 Figure 61.0 Figure 62.0 Figure 63.0 Figure 64.0 Figure 65.0 Figure 66.0 Figure 67.0 Figure 68.0 Figure 69.0 Figure 70.0 Figure 71.0 Figure 72.0 Figure 73.0 Figure 74.0 Figure 75.0 Figure 76.0 Figure 77.0 Figure 78.0 Figure 79.0 Figure 80.0 Figure 81.0 Figure 82.0 Figure 83.0 Figure 84.0 Figure 85.0 Figure 86.0 Figure 87.0 Figure 88.0 Figure 89.0 Figure 90.0 Figure 91.
TRI-PHASE OPERATING™ INSTRUCTIONS List of Appendicies APPENDIX A .................................................................................................................................141 APPENDIX B .................................................................................................................................
TRI-PHASE OPERATING™ INSTRUCTIONS 1.0 Introduction 1.1 Applicability This manual is applicable to the True Three-Phase Transformer Turns-Ratio (TRI-PHASE™) Tester model made by Vanguard Instruments Company, Inc. 2.0 General Description The TRI-PHASE™ is a true three-phase, field-portable, automatic transformer turns-ratio test instrument designed to conform to IEEE C57.12.90 measurement method.
TRI-PHASE OPERATING™ INSTRUCTIONS 3.0 Functional Description The TRI-PHASE™ measures a transformer turns-ratio from its windings by applying a 3-phase test voltage across the primary (H) winding and sensing the induced voltage on the secondary (X) winding. The measured voltage ratio between H and X is virtually the same as the turns-ratio of the windings because of no load on the windings during testing. The TRI-PHASE™ is capable of testing either single phase or three phase transformers.
TRI-PHASE OPERATING™ INSTRUCTIONS 3.0 Functional Description (continued) • The TTRA software application is compatible with Microsoft Windows XP, and Microsoft Windows Vista (see section 11.3 for more details). • Capable of raising or lowering the Load Tap Changer (LTC) tap position from the TRIPHASE™ front panel with the built-in LTC controller (see section 24.0 for more details). 4.0 Principles of Operation The TRI-PHASE™ measures transformer turns-ratios (using the ANSI/IEEE C57.12.
TRI-PHASE OPERATING™ INSTRUCTIONS 5.0 Specifications TRI-PHASE™ specifications are listed in Table 1.0. Table 1.
TRI-PHASE OPERATING™ INSTRUCTIONS 6.0 Supplied Cables Table 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 6.1 Cable Marking and Identification Both the H and X cable test leads are terminated with heavy-duty battery clips. Test cable leads are identified as follows. Table 3.
TRI-PHASE OPERATING™ INSTRUCTIONS 7.0 7.1 TRI-PHASE™ Front Panel Descriptions TRI-PHASE™ Operating Controls, Indicators and Connectors Figure 1.
TRI-PHASE OPERATING™ INSTRUCTIONS 7.1 TRI-PHASE™ Operating Controls, Indicators and Connectors (continued) Table 4.0 Fig. 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 8.0 TRI-PHASE™ Printer and Printer Paper The TRI-PHASE™ built-in thermal printer uses 4.5-inch wide thermal paper for printing test results. In order to maintain the highest quality printing and to avoid paper jams we recommend using the paper supplied by our factory. Paper can be ordered from the following sources. Vanguard Instruments Co, Inc. 1520 S. Hellman Ave. Ontario, CA 91761 Tel: 909-923-9390 Fax: 909-923-9391 Part Number: TP-4 Paper OR BG Instrument Co. 13607 E.
TRI-PHASE OPERATING™ INSTRUCTIONS 11.0 Special Features 11.1 LCD Contrast Control To darken the LCD display, press and hold the “V Contrast” switch for more than two seconds. To lighten the LCD display, press and hold the “W Contrast” switch for more than two seconds. 11.2 Test Voltages The TRI-PHASE™ has three selectable test voltages: 8Vac, 40Vac, and 100Vac. The TRIPHASE™ has two selectable test frequencies, 50 Hz and 60 Hz. Refer to Table 19.0 for test voltage selection. 11.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.0 Typical Cable Hook Up Configurations Always ground the TRI-PHASE™ with the provided ground cable contained in the cable set before connecting H and X cables. Ground the transformer bushings before connecting test leads to transformer. This procedure prevents inducing any voltages into the TRI-PHASE™. All transformer buss connections must be removed and transformer isolated before performing testing of transformer.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.2 Typical Cable Connections to a Delta-Wye Transformer (continued) X Cable LTC Control Cable Gnd Cable Power Cable H Cable Figure 3.0 Typical Front Panel Cable Connectors X Cable Connections H Cable Connections Figure 4.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.3 Single Phase Transformer Typical Connections Figure 5.0 Figure 6.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.4 Voltage Regulator Typical Connections Figure 7.0 Type A Voltage Regulator Typical Connections Figure 8.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.5 Donut Type (un-mounted) Current Transformer (CT) Typical Connections Figure 9.0 Donut Type (un-mounted) Current Transformer (CT) Typical Connections NOTE: H and X test leads are reversed for the CT ratio test shown above.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.6 Multi-tap CT Typical Connections Figure 10.0 Multi-tap CT Typical Connections 12.7 Bushing-Mount-CT on A Typical Single Phase Transformer Connections Figure 11.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.8 Bushing Mount CT’s on Typical Delta Transformer Connections NOTE: Install jumper on the unused winding Figure 12.0 Bushing Mount CT’s on Typical Delta Transformer Connections NOTE: The CT turns-ratio is obtained by performing a YNd test. Install jumpers on transformer secondary windings.
TRI-PHASE OPERATING™ INSTRUCTIONS 12.9 Bushing Mount CT’s on Typical Wye Transformer Connection Figure 13.0 Bushing Mount CT’s on Typical Wye Transformer Connection NOTE: The CT turns-ratio is obtained by performing an YNyn test. Install jumpers on transformer primary windings.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.0 Single-Phase Transformer Test Procedure Table 7.0 shows the procedure to test a single-phase transformer (2,400 V/240 V). Detailed descriptions of each menu are provided in the following sub-sections. Refer to Figure 1.0 for location of controls. The precondition for the following test procedure is that no previous singlephase transformer test has been performed (i.e.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.0 Single-Phase Transformer Test Procedure (continued) Table 5.0 Single-Phase Transformer Test Procedure (continued) STEP DESCRIPTION DISPLAY ACTION 8 “Start/Stop Test Status Display” “START” TO TEST OR “STOP” TO ABORT 9 “Test in Progress” status display TEST IN PROGRESS PLEASE WAIT… 10 “Test Results Status Display” Observe ratio, excitation current, and percentage error on LCD display RATIO +10.005 mA 1.9 %DIFF 0.
TRI-PHASE OPERATING™ INSTRUCTIONS Single-Phase Transformer Test Procedure (continued) 13.0 Table 5.0 STEP 18 Single-Phase Transformer Test Procedure (continued) DESCRIPTION DISPLAY “Record Saved” confirmation status display Test results saved in FLASH EEPROM as a test record ACTION RECORD NUMBER # HAS BEEN SAVED Press any Key or push down Control Knob 1.RUN TEST 2.SETUP 3.TEST PLAN 4.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.1 Main Menu 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:05 DATE: 07/16/08 Figure 14.0 Main Menu a. Description: The “Main Menu” (i.e., “start-up”) provides selection of the primary functions of the TRI-PHASE™. These functions consist of one or more sub-menus that allow the operator to test a transformer, select various settings or options, select test plan options, or perform diagnostics on the TRI-PHASE™. b.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.2 Transformer Configuration Selection Menu XFMR CONFIG: 1.SINGLE PHASE 2.Dy 3.Yd 4.Dd 5.Yy 6.Next Page Figure 15.0 Transformer Configuration Selection First Menu XFMR CONFIG: 1.Dz 2.Zd 3.Yz 4.Zy 5.TT 6.Previous Page Figure 16.0 Transformer Configuration Selection Second Menu a. Description: Either “Transformer Configuration Selection Menu” above will allow the operator to select the transformer type to be tested. There are two menus for this selection.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.3 Transformer Name Plate Voltage Menu XFMR NAME PLATE VLTG 1.YES 2.NO Figure 17.0 Transformer Nameplate Voltage Menu a. Description: This menu provides access to the “Name Plate Voltage” status display (Figure 18.0) for entry of the transformer nameplate voltages which are used to derive a calculated turns-ratio. The calculated turns-ratio is then used to compare the measured turns-ratio and calculate a percentage error reading. b.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.4 Transformer Voltage Data Entry Status Displays NAME PLATE VOLTAGE: H : X 0 : Figure 18.0 Name Plate Voltage Status Display NAME PLATE VOLTAGE: H : X 2,400 : Figure 19.0 Name Plate Voltage Display, H Voltage Keyed In NAME PLATE VOLTAGE: H : X 2,400 : 0 Figure 20.0 Name Plate Voltage Display, H Voltage Entered NAME PLATE VOLTAGE: H : X 2,400 : 240 Figure 21.0 Name Plate Voltage Display, X Voltage Keyed In a.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.5 Start/Stop Test Status Display “START” TO TEST OR “STOP” TO ABORT Figure 22.0 Start/Stop Test Status Display a. Description: Allows the operator to start to test or abort a test. b. Origin: The LCD displays “Start/Stop Test Status Display” after the operator enters the nameplate voltage for X (Figure 21.0) or selects 2 on the “Transformer Name Plate Voltage Menu” (Figure 17.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.6 Test In Progress Status Display TEST IN PROGRESS PLEASE WAIT… Figure 23.0 Test In Progress Status Display a. Description: The “Test In Progress Status Display” (Figure 23.0) is displayed when the turns-ratio test is performed. b. Origin: The LCD displays the “Test In Progress Status Display” after the operator presses the “START” key (Figure 22.0). c. Action Options: None. d. Action To Perform: Observe status.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.7 Test Results Status Display RATIO mA %DIFF +10.005 1.9 0.05 Figure 24.0 Test Results Status Display a. Description: Displays the transformer winding polarity, turns-ratio, excitation current (in milliamps), and turns-ratio percentage error after completion of the transformer test. A typical turns-ratio test result screen is shown in Figure 24.0. The display result is explained below: Ratio displayed: Polarity displayed: Excitation current: Percentage error: 10.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.8 Print Test Results Menu PRINT TEST RESULTS? 1.YES 2.NO Figure 25.0 Print Test Results Menu a. Description: The TRI-PHASE™ has the capability to print the current test results (displayed on the LCD screen) using the built-in thermal printer. b. Origin: The “Print Test Results Menu” is displayed after operator presses any key or pushes down on the Control Knob from the “Test Result Status Display” (Figure 24.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS pushing down on the Control Knob after number 2 is selected. d. Action To Perform: Select menu option 1 for this example. e. Results of Action: Once the desired print format is selected the test results are printed and the LCD displays the “Keep This Reading Menu” (Figure 29.0).
TRI-PHASE OPERATING™ INSTRUCTIONS 13.10 Test Result Column Format Printout 1 2 3 4 5 6 7 8 12 11 Figure 27.0 10 9 Single Phase Column Format Printout A typical single-phase transformer test results printout in column format is shown in Figure 27.0. The test results printout is explained below. 1. Test record time and date is printed at the top of the printout 2. Test voltage is 40 volts at 60 Hz for this test. Refer to section 11.2 for more details about test voltages and frequencies 3.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.11 Test Result Detail Format Printout 1 2 3 4 5 6 7 8 9 10 11 Figure 28.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.11 Test Result Detail Format Printout (continued) The same report is now shown in detailed format printout (Figure 28.0). The test results detail printout is explained below. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Test record time and date is printed at the top of the printout Test voltage is 40 volts at 60 Hz for this test. Refer to paragraph 11.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.12 Keep This Reading Menu KEEP THIS READING? 1.YES 2.NO Figure 29.0 Keep This Reading Menu a. Description: The operator has the option to store the current test result in non-volatile memory or disregard the current test results. b. Origin: After the operator selects 1 (“YES”) or the operator selects 2 (“NO”) from the “Print Test Results Menu” (Figure 25.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.13 Previous Data In Buf. Menu PREVIOUS DATA IN BUF. 1. APPEND PREV. DATA 2. CLEAR PREV. DATA Figure 30.0 Previous Data In Buf Menu a. Description: This menu is displayed when there is an existing test result in memory of the same type of transformer which is under test. The “Append Previous Data” feature allows the operator to stop the testing in order to perform other duties.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.14 Run Another Test Menu RUN ANOTHER TEST? 1.YES 2. NO 3. REPEAT PREV. TEST Figure 31.0 Run Another Test Menu a. Description: Allows the selection of performing another test on the transformer, ending testing, or repeating the previous test. b. Origin: After the “Test Saved Status Display”. Refer to “Keep This Reading” section 13.12.d. c. Action Options: Press key number 1 (“YES”) or push down the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.15 Save This Record Menu SAVE THIS RECORD? 1.YES 2.NO Figure 32.0 Save This Record Menu a. Description: Allows for the transfer of current test results from the non-volatile memory into FLASH EEPROM. Up to 112 test-records may be stored in FLASH EEPROM. b. Origin: After selecting key 2 from the “Run Another Test Menu” (Figure 31.0). c. Action Options: Press key number 1 (“YES”) or push down the Control Knob to save the current test results to a test record.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.16 Record Saved Confirmation Status RECORD NUMBER # HAS BEEN SAVED! Figure 33.0 Record Saved Confirmation Status Display a. Description: The current test results are saved into the next sequential test record number (#) assigned. The test record is saved in FLASH EEPROM. b. Origin: Select menu option 1 (“YES”) from the “Save This Record Menu” (Figure 32.0). c. Action Options: Press any key or push down the Control Knob to return to the “Main Menu” (Figure 14.0). d.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.17 Transformer Name Plate Voltage Menu For Another Test XFMR NAME PLATE VLTG 1.YES 2.NO 3.USE PREVIOUS DATA Figure 34.0 Nameplate Voltage Selection Menu For Another Test a. Description: This menu displays when another test is performed. The operator has an added option to use the same nameplate voltage data from the previous test. b. Origin: After selecting number 1 (“YES”) from the options listed in “Run Another Test Menu” (Figure 31.
TRI-PHASE OPERATING™ INSTRUCTIONS 13.18 Test Record Not Saved Menu ARE YOU SURE? DATA WILL BE LOST! 1.DO NOT SAVE RECORD 2.SAVE RECORD Figure 35.0 Test Record Not Saved Menu a. Description: This menu displays after the operator decides to not save the test results to a test record. b. Origin: Press key number 2 (“NO”) from the “Save This Record Menu” (Figure 32.0). c. Action Options: Press key number 1 or push down the Control Knob to select not to save the test results to a test record.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.0 Dyn1 Transformer Test Procedure Table 6.0 shows the procedure to test a Dyn1 (12,000 V/208 V) transformer. Table 6.0 STEP Dyn1 Transformer Test Procedure DESCRIPTION DISPLAY ACTION Press key number 1 or push down Control Knob 1 Select “Run Test” from “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 2 Select “Dy” (Delta to Wye) from the “Transformer Configuration” first menu XFMR CONFIG: 1. SINGLE PHASE 2. Dy 3.Yd 4.Dd 5.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.0 Dyn1 Transformer Test Procedure (continued) Table 6.0 Dyn1 Transformer Test Procedure (continued) STEP DESCRIPTION DISPLAY 10 “Test in Progress Status Display” TEST IN PROGRESS PLEASE WAIT… None 11 “Test Results Status Display” Observe ratio, excitation current, and percentage error on LCD display RATIO mA %DIFF A 57.757 2.3 0.11 B 57.754 2.4 0.11 C 57.741 3.4 0.08 XFMR TYPE: Dyn1 None Three-phase test turns-ratio results are shown first.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.0 Dyn1 Transformer Test Procedure (continued) Table 6.0 Dyn1 Transformer Test Procedure (continued) STEP DESCRIPTION DISPLAY ACTION Select “NO” from the “Run Another Test Menu” RUN ANOTHER TEST? 1.YES 2.NO 3. REPEAT PREV. TEST Store test results in FLASH EEPROM SAVE THIS RECORD? 1.YES 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.1 Delta-To-Wye (Dyn) Transformer Test Column Format Printout 1 2 3 4 5 6 7 8 9 Figure 36.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.1 Delta-To-Wye (Dyn) Transformer Test Column Format Printout (continued) The delta-wye test results printout is explained below for Figure 36.0. 1. 2. 3. 4. 5. 6. 7. 8. 9. Test record time and date is printed at the top of the printout. Test voltage is 40 volts at 60 Hz for this test. Refer to paragraph 19.0 for more details about test voltages and frequencies. Type of transformer under test is Delta to Wye with X0 available (Dyn1).
TRI-PHASE OPERATING™ INSTRUCTIONS 14.2 Delta-To-Wye Transformer Test Detail Format Printout 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Figure 37.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.2 Delta-To-Wye Transformer Test Detail Format Printout (continued) 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 Figure 37.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.2 Delta-To-Wye Transformer Test Detail Format Printout (continued) The same 3-phase test results are now shown in detailed format printout (Figure 37.0). The test results printout is explained below: 1. 2. 3. 4. 5. 6 7 8 9 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. Test record time and date is printed at the top of the printout. Test voltage is 40 volts at 60 Hz for this test. Refer to section 11.
TRI-PHASE OPERATING™ INSTRUCTIONS 14.2 Delta-To-Wye Transformer Test Detail Format Printout (continued) 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. 46. 47. 48. 49. 50. 51. 52. 53. 54. Single Phase Test Results (numbers 31 through 54). Test H1-H3 and X1-X0 heading. H1-H3 tap voltage is 12,000 volts. X1-X0 tap voltage is 208 volts. H1-H3, X1-X0 name plate calculated voltage ratio is 99.926. H1-H3, X1-X0 measured voltage ratio is 100.06.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.0 Test Record Options 16.1 Restore A Test Record To Print Procedure The following procedure allows the operator to restore a test record from FLASH EEPROM. Table 7.0 STEP Restore A Test Record To Print Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 2 Selection of 2 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.1 Restore A Test Record Procedure (continued) Table 7.0 STEP Restore A Test Record To Print Procedure (continued) DESCRIPTION DISPLAY “Print Format Menu” Select either print format PRINT FORMAT? 1.COLUMN 2.DETAILED 10 Test record is printed PLEASE WAIT… PRINTING REPORT 11 Return to “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 9 60 ACTION . Press key number 1 or key number 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.2 Setup Menu 1.RECORD ID . 2.TEST VOLTAGE 3.TEST FREQUENCY 4.PRINT RECORD 5.SAVE/RESTORE RECORD 6.SET TIME Figure 38.0 Setup Menu a. Description: Allows the operator to select other operational features of the TRI-PHASE™ test device. b. Origin: From the “Main Menu” (Figure 14.0) select menu option 2. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.3 Save/Restore Record Menu 1.RESTORE RECORD 2.SAVE RECORD 3.RECORD DIRECTORY 4.ERASE RECORD . Figure 39.0 Save/Restore Record Menu a. Description: Allows the operator to restore a test record, save a test record, print a directory of test records, erase a single test record, or erase all test records. b. Origin: From the “Setup Menu” (Figure 38.0) select menu option 5. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.4 Restore Record Menu RESTORE RECORD 1.ENTER RECORD NUMBER 2.SCROLL TO SELECT . Figure 40.0 Restore Record Menu a. Description: Allows the operator to restore a test record. b. Origin: From the “Save/Restore Record Menu” (Figure 39.0) select menu option 1. c. Action Options: Press key number 1 or push down on the Control Knob to select “Enter Record Number” option. Press key number 2 to select “Scroll To Select” option.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.5 Restore Record Number Status Display RESTORE RECORD NUMBER: Figure 41.0 Restore Record Number Status Display a. Description: The operator enters the record number to restore. b. Origin: From the “Restore Record Menu” (Figure 40.0) selection menu option 1. c. Action Options: Enter the record number to restore by pressing on the key numbers 0 through 9 and pressing “ENTER” to confirm.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.6 Record Restored Menu RECORD RESTORED! PRINT RECORD? 1.YES 2.NO . Figure 42.0 Record Restored Menu a. Description: Allows the operator to decide to print or not print the restored record. Selecting menu option 1 (“YES”) allows for viewing of the record on the LCD screen or printing to the printer. b. Origin: Pressing “ENTER” from the “Restore Record Number Status Display” after test record number is keyed in (Figure 41.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.7 Print Record To LCD Or Printer Menu PRINT RECORD 1.PRINT TO LCD 2.PRINT TO PRINTER . Figure 43.0 Print Record Menu a. Description: Allows the operator to decide to display the restored test record on the LCD or print the restored record. b. Origin: Selecting menu option 1 (“YES”) from the “Record Restored Menu” (Figure 42.0). c. Action Options: Press key number 1 to select “PRINT TO LCD” option.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.8 Print Format Menu PRINT FORMAT? 1.COLUMN 2.DETAILED . Figure 44.0 Print Format Menu a. Description: Allows the operator to select which format to use for printing the test record. Refer to Figure 45.0 for a typical test record column format printout. Refer to Figure 46.0 for a typical test record detailed format printout. b. Origin: This menu is displayed after the operator selects menu option 2 from the “Print Record Menu” (Figure 43.0 Print Record Menu). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.9 Test Record Printout Column Format Figure 45.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.10 Test Record Printout Detailed Format Figure 46.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.10 Test Record Printout Detailed Format (continued) Figure 46.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.11 Save Test Results To A Test Record Procedure The following procedure allows the operator to save test results to a test record. The operator may perform one or more transformer tests of an identical transformer configuration, each time saving the test results in working memory. All of the test results remain in the temporary memory at the completion of the testing.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.12 Print Test Record Directory The following procedure allows the operator to print the directory of test records stored in FLASH EEPROM. Table 9.0 STEP 1 2 3 4 5 Print Test Record Directory Procedure DESCRIPTION Select “Setup” from the “Main Menu” Select “Save/Restore Record” from the “Setup Menu” Select “Record Directory” from the “Save/Restore Menu” DISPLAY ACTION 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 .
TRI-PHASE OPERATING™ INSTRUCTIONS 16.13 Print Directory Menu PRINT DIRECTORY 1.FULL DIRECTORY 2.SHORT DIRECTORY . Figure 47.0 Print Directory Menu a. Description: Allows the operator to print a short directory or full directory of test record headers. Selecting the short directory will print the last ten record headers stored in FLASH EEPROM. Selecting the full directory will print all test record headers stored in FLASH EEPROM. b. Origin: From the “Save/Restore Menu” (Figure 39.0) select menu option 3.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.14 Record Directory Printout The TRI-PHASE™ record directory printout shows a total of 3 records stored in FLASH EEPROM memory. Record #33 is a single-phase transformer with one test result in record. Record #34 is a single-phase transformer with two test results in record. Record #35 is a Delta to Wye transformer with one test result in record. 1 2 3 4 5 6 7 8 9 10 Figure 48.0 Record Directory Printout The test results printout is explained below: 1. 2. 3. 4. 5. 6. 7.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.15 Restore Test Record To LCD Procedure The following procedure allows the operator to restore a test record from FLASH EEPROM and display it on the LCD for viewing. Table 10.0 STEP Restore Test Record To LCD Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 2 Selection of 2 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.15 Restore Test Record To LCD Procedure (continued) Table 10.0 Restore Test Record To LCD Procedure (continued) STEP DESCRIPTION 7 “Restored Record Status Display” Observe test record displayed on LCD #43 07/17/08 1 TESTS “Record Restored Menu” Record recalled from FLASH EEPROM to temporary memory RECORD RESTORED! PRINT RECORD? 1.YES 2.NO “Print Record Restored Menu” Display test record to LCD or print test record PRINT RECORD 1.PRINT TO LCD 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.16 Scroll Test Record Menu RECORDS DIRECTORY “UP” TO SCROLL FWD “DWN” TO SCROLL RVS Figure 49.0 Scroll Test Record Menu a. Description: Allows the operator to scroll in forward or reverse order through all of the test records stored in FLASH EEPROM. b. Origin: This menu is displayed after the operator selects menu option 2 from the “Restore Record Menu” (Figure 40.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.17 Restored Record Status Display 1 2 #43 07/17/08 1 TESTS 07:28:59 3 4 5 FACTORY 120V 120V ABC TEST TRANSFORMER 6 Figure 50.0 Restored Record Status Display The restored test record header is displayed on the LCD screen. 1. 2. 3. 4. 5. 6.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.18 Record Restored Menu RECORD RESTORED! PRINT RECORD? 1.YES . 2.NO Figure 51.0 Record Restored Menu a. Description: Allows the operator to decide to print or not print the restored record. Deciding not to print the test record allows for viewing of the record on the LCD screen. b. Origin: Selecting menu option 1 (“YES”) from the “Restore Record Status Display” (Figure 50.0). c. Action Options: Press key number 1 to select “YES”.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.19 Print Record Restored Menu PRINT RECORD 1.PRINT TO LCD 2.PRINT TO PRINTER . Figure 52.0 Print Record Restored Menu a. Description: Allows the operator to decide to display the restored test record on the LCD or print the restored record. b. Origin: Selecting menu option 1 (“YES”) from the “Record Restored Menu” (Figure 51.0). c. Action Options: Press key number 1 to select “PRINT TO LCD” option. Press key number 2 to select “PRINT TO PRINTER” option.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.20 Restored Record Status Displays SINGLE PHASE Num Tests: 1 07/17/08 07:28:59 FACTORY 120 ABC TEST TRANSFORMER Figure 53.0 Restored Record First Status Display 1 SINGLE PHASE 40 VOLTS 60 Hz SINGLE-PHASE RESULTS: RATIO mA %DIFF +10.005 1.9 0.05 Figure 54.0 Restored Record Second Status Display a. Description: The test record is displayed on the LCD in two displays. b. Origin: Selecting menu option 1 (“YES”) from the “Print Record Restored Menu” (Figure 52.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.21 Erase A Test Record Procedure The following procedure allows the operator to erase a test record from FLASH EEPROM memory. Table 11.0 STEP Erase A Test Record Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 2 Selection of 2 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.22 Erase Record Menu ERASE RECORD 1.ERASE SINGLE RECORD 2.ERASE ALL RECORDS . “STOP” TO EXIT Figure 55.0 Erase Record Menu a. Description: Allows the operator to erase a single test record, or erase all test records from FLASH EEPROM. b. Origin: From the “Save/Restore Record Menu” (Figure 39.0) select menu option 4. c. Action Options: Press key number 1 or push down on the Control Knob to select the “Erase Single Record” option.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.23 Erase Record Status Display ERASE RECORD NUMBER: Figure 56.0 Erase Record Status Display a. Description: Allows the operator to enter the test record number to be erased. b. Origin: From the “Erase Record Menu” (Figure 55.0) select menu option 1. c. Action Options: Enter the record number to erase by pressing on the key numbers 0 through 9 and pressing “ENTER” or push down Control Knob to confirm.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.24 Record Number Erased Confirmation Status Display RECORD NUMBER 50 ERASED! Figure 57.0 Record Number Erased Status Display a. Description: Confirmation of test record erased from FLASH EEPROM memory. b. Origin: After keying in the test record number to be erased and pressing the “ENTER” key. c. Action To Perform: Press “STOP” to return the “Main Menu” for this example.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.25 Erase All Test Records Procedure The following procedure allows the operator to erase all test records from FLASH EEPROM. Table 12.0 STEP Erase All Test Records Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 2 Selection of 2 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.26 Erase All Records Status Display ERASE ALL RECORDS! ARE you SURE? “ENTER” TO CONTINUE. Figure 58.0 Erase All Records Status Display a. Description: Allows the operator to erase all test records from FLASH EEPROM. b. Origin: From the “Erase Record Menu” (Figure 55.0) select menu option 2. c. Action Options: Press “ENTER” to confirm to erase all test records. Press “STOP” to abort and return to “Main Menu”. d.
TRI-PHASE OPERATING™ INSTRUCTIONS 16.27 Record Number Erased Confirmation Status Display RECORDS ERASED! Figure 59.0 Records Erased Status Display a. Description: Confirmation that all test records have been erased from FLASH EEPROM memory. b. Origin: After pressing “ENTER” or pushing down Control Knob from the “Erase All Records” status display. c. Action To Perform: Press any key or push down Control Knob to return the “Main Menu”.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.0 Test Plan Options 17.1 Load a Test Plan and Test a Transformer Procedure Table 13.0 shows the procedure to test a single-phase transformer using a test plan for this example. This procedure may be used for any transformer configuration. Each of the menus is described in detail in the following paragraphs. Table 13.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.1 Load a Test Plan and Test a Transformer Procedure (continued) Table 13.0 STEP Load a Test Plan and Test a Transformer Procedure (continued) DESCRIPTION DISPLAY ACTION 8 “Testing In Progress Status Display” TEST IN PROGRESS PLEASE WAIT… None 9 “Test Results Status Display” SINGLE PHS TEST RSLT: RATIO mA %DIFF A+99.985 2.6 0.06 P B+100.08 1.8 0.16 P C+99.994 2.4 0.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.1 Load a Test Plan and Test a Transformer Procedure (continued) Table 13.0 STEP 17 Load A Test Plan And Test Transformer Procedure (continued) DESCRIPTION “Record Saved Status Display” DISPLAY ACTION RECORD NUMBER 60 HAS BEEN SAVED! Press any key or push down Control Knob to return to “Main Menu” Test record 60 saved for this example Test results saved in FLASH EEPROM to a test record confirmation 18 “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.2 Test Plan Menu 1.LOAD TEST PLAN 2.UNLOAD TEST PLAN 3.PLAN DIRECTORY 4.PRINT TEST PLAN 5.ERASE TEST PLAN 6.SAVE TEST PLAN Figure 60.0 . Test Plan Menu a. Description: Allows the operator to select various test plan options. b. Origin: From the “Main Menu” (Figure 14.0) select menu option 3. c. Action Options: Press key number 1 or push down on the Control Knob to select the “Load Test Plan” status display.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.3 Load Test Plan Number Status Display LOAD TEST PLAN NUMBER: Figure 61.0 Load Test Plan Number Status Display a. Description: Allows the operator to enter a test plan number to test a transformer. The pass/fail test requirements for %DIFF are defined in the test plan. This enables the printing of the pass/fail status of the test. b. Origin: From the “Test Plan Menu” select menu option 1. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.4 Test Plan Loaded Menu TP# 1 TAPS: 1 Dyn1 TEST PLAN LOADED 1.CONTINUE . 2.UNLOAD TEST PLAN Figure 62.0 Test Plan Loaded Menu a. Description: Confirms that test plan 1 (i.e., “TP#1) is loaded in temporary memory. Allows the operator to perform a transformer test using test plan 1 or perform a test with the operator inputting the test parameters (i.e., refer to step 2 of Table 5.0 or step 2 of Table 6.0).
TRI-PHASE OPERATING™ INSTRUCTIONS 17.5 Test Plan Loaded Status Display TAP NUMBER 1 H VTG: 12,000 X VTG: 208 “START” to RUN TEST Figure 63.0 Test Plan Loaded Status Display a. Description: Displays H and X voltages set by test plan test number 1 used for testing the transformer. b. Origin: With a test plan loaded in temporary memory, select menu option 1 from the “Test Plan Loaded Menu”. c. Action Options: Press “START” to perform test number 1.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.6 Test Plan Test Results Status Display SINGLE PHS TEST RSLT: RATIO mA %DIFF A+99.985 2.6 0.06 P B+100.08 1.8 0.16 P C+99.994 2.4 0.07 P XFMR TYPE: Dyn1 Figure 64.0 Test Plan Test Results Status Display a. Description: The single phase test results of the measured transformer turns-ratio, excitation current, percentage error, and “PASS/FAIL” (i.e., P for pass, F for fail) status is displayed for this test.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.7 Print Test Plan Test Results a. Description: The TRI-PHASE™ has the capability to print the test plan test results using the built-in thermal printer. b. Origin: The “Print Test Results Menu” (Figure 25.0) is displayed after operator presses any key or pushes down on the Control Knob from the “Test Plan Test Result Status Display” (Figure 64.0) c. Action Options: Refer to the “Print Format Menu” (Figure 26.0).
TRI-PHASE OPERATING™ INSTRUCTIONS 17.8 Test Plan Test Results Printout PASS/FAIL INDICATION Figure 65.0 Test Plan Test Results Printout Column Format NOTE: “PASS” or “FAIL” status is shown as “P” or “F” next to the “%DIFF” printout. The Pass/Fail parameter for this test is %DIFF of 0.5%.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.9 Unload a Test Plan Procedure The following procedure allows the operator to clear a test plan from the FLASH EEPROM nonvolatile memory. Table 14.0 STEP Unload A Test Plan Procedure DESCRIPTION DISPLAY ACTION 1 Select “Test Plan” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 3 Selection of 3 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.10 Print Test Plan Directory Procedure The following procedure allows the operator to print the test plan directory stored in FLASH EEPROM non-volatile memory. Table 15.0 STEP Print Test Plan Directory Procedure DESCRIPTION DISPLAY ACTION 1 Select “Test Plan” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 3 Selection of 3 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.11 Test Plan Directory Print Out Typical Test Plan Directory is shown in Figure 66. 2 1 3 Figure 66.0 Test Plan Directory Print Out The Test Plan Direct Printout is explained below. 1. 2. 3.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.12 Print Test Plan Procedure Table 16.0 shows the procedure to perform for printing a transformer test plan stored in FLASH EEPROM. Transformer test plans contain the transformer nameplate voltages for each test (i.e., TAP). The calculated ratios (derived from the transformer name plate voltage) are then compared with the measured ratios and the percentage error is calculated (i.e., %DIFF).
TRI-PHASE OPERATING™ INSTRUCTIONS 17.13 Print Test Plan Status Display PRINT TEST PLAN NUMBER: Figure 67.0 Print Test Plan Status Display a. Description: Allows the operator to enter the test plan to be printed. The test plan header information will be printed. b. Origin: From the “Test Plan Menu” (Figure 60.0) select menu option 4. Selection of 4 may be made by turning the Control Knob. Push down the Control Knob after option 4 is selected. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.14 Typical Three Phase Dyn1 Test Plan Printout The test plan test parameters are displayed in Figure 68.0. 1 2 3 4 Figure 68.0 Typical Three Phase Dyn1 Test Plan Printout The test plan direct printout is explained below. 1. 2. 3. 4. Maximum %Diff limit Number of tests (i.e.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.15 Erase A Test Plan Procedure The following procedure allows the operator to erase a test plan stored in FLASH EEPROM nonvolatile memory. Table 17.0 STEP Erase A Test Plan Procedure DESCRIPTION DISPLAY ACTION 1 Select “Test Plan” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 3 Selection of 3 may be made by turning the Control Knob.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.16 Erase Test Plan Menu ERASE TEST PLAN 1.ERASE SINGLE PLAN 2.ERASE ALL PLANS . Figure 69.0 Erase Test Plan Menu a. Description: Allows the operator to erase a single test plan, or erase all test plans from FLASH EEPROM. b. Origin: From the “Test Plan Menu” (Figure 60.0) select menu option 5. c. Action Options: Press key number 1 or push down on the Control Knob to select the “Erase Single Plan” option. Press key number 2 to select “Erase All Plans” option.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.17 Erase Test Plan Status Display ERASE TEST PLAN NUMBER: Figure 70.0 Erase Test Plan Status Display a. Description: Allows the operator to enter the test plan number to be erased. b. Origin: From the “Erase Test Plan Menu” (Figure 69.0) select menu option 1. c. Action Options: Enter the test plan number to erase by pressing on keys number 0 through 9 and pressing “ENTER” or pushing down the Control Knob to confirm.
TRI-PHASE OPERATING™ INSTRUCTIONS 17.18 Test Plan Number Erased Confirmation Status Display TEST PLAN NUMBER 5 ERASED! Figure 71.0 Test Plan Number Erased Status Display a. Description: Confirmation of test plan number erased from FLASH EEPROM memory. b. Origin: After confirming the test plan to be erased. c. Action To Perform: Press any key or push down the Control Knob to return to the “Main Menu”.
TRI-PHASE OPERATING™ INSTRUCTIONS 18.0 Entering Test Record Identification Information Procedure The following procedure allows the operator to enter transformer identification information for the test record ID. This information is printed on each test record printout. Table 18.0 STEP Entering Test Record Identification Information Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 .
TRI-PHASE OPERATING™ INSTRUCTIONS Table 18.
TRI-PHASE OPERATING™ INSTRUCTIONS 19.0 Test Voltage Selection Procedure Table 19.0 shows the procedure to perform in order to select a transformer test voltage. Refer to section 19.1 for a description of the available transformer test voltages. Table 19.0 STEP Transformer Test Voltage Selection Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 .
TRI-PHASE OPERATING™ INSTRUCTIONS 19.1 Test Voltage Selection The TRI-PHASE™ has the capability to output three different test voltages of 8Vac, 40Vac, or 100Vac. The test voltages are generated by an internal oscillator. • • • The 8Vac test voltage is for testing transformers which require low test voltages, such as metering Current Transformers (CT). Higher test voltages may drive the CT's into saturation giving invalid results. The 40Vac test voltage is recommended for testing power transformers.
TRI-PHASE OPERATING™ INSTRUCTIONS 20.0 Test Frequency Selection Procedure Table 20.0 shows the procedure to perform in order to select a transformer test frequency. Refer to section 20.1 for a description of the available transformer test frequencies. Table 20.0 STEP Transformer Test Frequency Selection Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup” from “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 .
TRI-PHASE OPERATING™ INSTRUCTIONS 20.1 Test Frequency Selection The TRI-PHASE™ has the capability to output two different test frequencies of 50 Hz or 60 Hz. The test frequencies are generated by an internal oscillator. The test frequencies are selected either when using the “Computer Interface Mode” or from the keypad. 1. 60 Hz 2. 50 Hz . Figure 73.0 Test Frequency Selection Menu a. Description: The operator selects the desired test frequency (50 Hz or 60 Hz).
TRI-PHASE OPERATING™ INSTRUCTIONS 21.0 Change Date And Time Procedure The following procedure allows the operator to change the TRI-PHASE™ date and time. Table 21.0 STEP Change Date and Time Procedure DESCRIPTION DISPLAY ACTION 1 Select “Setup Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 . Press key number 2 Selection of 2 may be made by turning the Control Knob. Push down Control Knob after 2 is selected 2 Select “Set Time Menu” 1.RECORD ID . 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 21.1 Enter Date Status Display ENTER DATE MM-DD-YY Figure 74.0 Enter Date Status Display a. Description: The date is stored in a battery powered volatile memory. The time and date are displayed on the lower portion of the LCD when the TRI-PHASE™ is operational. b. Origin: From the “Start Up Menu”, press key number 6. Selection of number 6 may be made by turning the Control Knob. Push down the Control Knob after number 6 is selected. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 21.2 Enter Time Status Display ENTER TIME HH-MM-SS Figure 75.0 Enter Time Status Display a. Description: The time is stored in a battery powered volatile memory. The time and date are displayed on the lower portion of the LCD when the TRI-PHASE™ is operational. b. Origin: Immediately after entering the last digit of the date from step c of section 21.1. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 22.0 H And X Cable Diagnostic Test Procedure The following procedure allows the operator to perform diagnostics on the TRI-PHASE™ H and X cables. Table 22.0 H And X Cable Diagnostic Test Procedure STEP DESCRIPTION DISPLAY ACTION 1 Select “Diagnostic” from “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 2 Select “Cable Test” from the “Diagnostic Menu” DIAGNOSTIC 1.CABLE TEST 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 23.0 TRI-PHASE™ Verification Test Procedure The following procedure allows the operator to perform a verification test on the TRI-PHASE™ electronics. Table 23.0 STEP TRI-PHASE™ Verification Test Procedure DESCRIPTION DISPLAY 1 Select “Diagnostic” from the “Main Menu” 1.RUN TEST 2.SETUP 3.TEST PLAN 4.DIAGNOSTIC TIME: 20:15:00 DATE: 07/16/08 2 Select “Verification Test” from the “Diagnostic Menu” DIAGNOSTIC 1.CABLE TEST 2.
TRI-PHASE OPERATING™ INSTRUCTIONS 24.0 Load Tap Changer A built-in Load Tap Changer (LTC) controller provides the capability to raise or lower the LTC tap position from the TRI-PHASE™ front panel. The LTC interface cable has four connectors that are color coded. The two green cable connectors are labeled “RAISE”, and two white cable connectors are labeled “LOWER”. LOWER fuse 250Vac/ 1A fast blow dry contact switches RAISE fuse 250Vac/ 1A fast blow Figure 76.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.0 USB FLASH Thumb Drive With the USB FLASH thumb drive inserted many of the operational menus described in this manual will contain an extra option to select the thumb drive. When this option is selected, the submenus will allow for selection of the internal FLASH EEPROM memory or the thumb drive FLASH memory. The following paragraphs describe each menu that has these added options and their related status displays. 25.1 Save/Restore Record With Thumb Drive Menu 1.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.2 Copy Record To Thumb Drive Menu COPY REC TO THUMB DRV 1.COPY SINGLE RECORD 2.COPY ALL RECORDS . Figure 78.0 Copy Record To Thumb Drive Menu a. Description: Allows the operator to copy a single record to the thumb drive or copy all records to thumb drive. b. Origin: From the “Save/Restore Record With Thumb Drive Menu” (Figure 77.0) select menu option 5. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.3 Copy Single Record To Thumb Drive Status Displays ENTER RECORD NUMBER TO COPY TO FLASH DRV NUMBER: REC_## SAVED TO THUMB DRIVE Figure 79.0 Copy Single Record To Thumb Drive Status Displays a. Description: Allows the operator to copy a single record to thumb drive. b. Origin: From the “Copy Record To Thumb Drive Test Menu” (Figure 78.0) select menu option 1. c. Action Options: Enter the record number to copy to the thumb drive using key numbers 0 through 9.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.4 Copy All Records To Thumb Drive Status Displays The following status displays when menu option 2 of “Copy To Thumb Drive Test Record Menu” has been selected. SAVING RECORD ## TO THUMB DRIVE PLEASE WAIT… ALL RECORDS HAVE BEEN TRANSFERRED TO THUMB DRIVE Figure 80.0 Copy All Records To Thumb Drive Status Displays a. Description: Status displays while each record is saved to thumb drive. The record numbers appear in sequential order. b.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.5 Test Plan With Thumb Drive Menu 1.LOAD TEST PLAN . 2.UNLOAD TEST PLAN 3.PLAN DIRECTORY 4.PRINT TEST PLAN 5.ERASE TEST PLAN 6.SAVE TEST PLAN 7.COPY TO THUMB DRIVE Figure 81.0 Test Plan With Thumb Drive Menu a. Description: Allows the operator to select various test plan operations. b. Origin: From the “Main Menu” (Figure 14.0) press key number 3. Selection of number 3 may be made by turning the Control Knob. Push down the Control Knob after number 3 is selected. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.6 Copy Test Plan To Thumb Drive Status Display ENTER TP NUMBER TO COPY TO FLASH DRV TP NUMBER: Figure 82.0 Copy Test Plan To Thumb Drive Status Display a. Description: Allows the operator to copy a test plan from internal memory to the thumb drive. b. Origin: This menu is displayed after the operator selects menu option 7 (“Copy To Thumb Drive”) from the “Test Plan With Thumb Drive Menu” (Figure 81.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.7 Test Plan Saved To Thumb Drive Confirmation Status Displays COPYING TEST PLAN TO THUMB DIRVE. PLEASE WAIT… TP## SAVED TO THUMB DRIVE AS PLAN_### Figure 83.0 Test Plan Saved To Thumb Drive Confirmation Status Displays a. Description: Confirmation of a test plan copied to thumb drive from internal memory. b. Origin: This menu is displayed after the operator selects the test plan number from the “Copy Test Plan To Thumb Drive” (Figure 82.0) status display. c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.8 Load Test Plan With Thumb Drive Menu 1.INTERNAL STORAGE 2.THUMB DRIVE . Figure 84.0 Load Test Plan Number With Thumb Drive Menu a. Description: Allows the operator to load a test plan from either the internal memory or from the thumb drive. b. Origin: This menu is displayed after the operator selects menu option 1 (“Load Test Plan”) from the “Test Plan With Thumb Drive Menu” (Figure 81.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.9 Load Thumb Drive Test Plan Status Displays LOAD THUMB DRIVE TP PLAN_ LOAD THUMB DRIVE TP PLAN_### Figure 85.0 Load Thumb Drive Test Plan Status Displays a. Description: Allows the operator to load a test plan from the thumb drive. b. Origin: This menu is displayed after the operator selects number 2 (“Thumb Drive”) from the “Load Test Plan Number With Thumb Drive Menu” (Figure 84.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.10 Print Test Plan Directory With Thumb Drive Menu 1.INTERNAL DIRECTORY 2.THUMB DRIVE DIR . Figure 86.0 Print Test Plan Directory With Thumb Drive Menu a. Description: Allows the operator to print a test plan directory from the internal memory or from the thumb drive. b. Origin: This menu is displayed after the operator selects menu option 3 (“Plan Directory”) from the “Test Plan With Thumb Drive Menu” (Figure 81.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.11 Print Test Plan With Thumb Drive Menu 1.PRINT INTERNAL TP 2.PRINT FLASH DRV TP . Figure 87.0 Print Test Plan With Thumb Drive Menu a. Description: Allows the operator to print a test plan from either the internal memory or from the thumb drive. b. Origin: This menu is displayed after the operator selects menu 4 (“Print Test Plan”) from the “Test Plan With Thumb Drive Menu” (Figure 81.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.12 Print Thumb Drive Test Plan Status Displays PRINT THUMB DRIVE TP PLAN_ PRINT THUMB DRIVE TP PLAN_### Figure 88.0 Print Thumb Drive Test Plan Status Displays a. Description: Allows the operator to enter a thumb drive test plan number to be printed. b. Origin: This menu is displayed after the operator selects menu option 1 (“Print Internal Tp”) from the “Print Test Plan With Thumb Drive Menu” (Figure 87.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.13 Erase Test Plan With Thumb Drive Menu 1.ERASE INTERNAL PLAN . 2.ERASE THUMB DRV PLAN Figure 89.0 Erase Test Plan With Thumb Drive Menu a. Description: Allows the operator to erase a test plan from the internal memory or from the thumb drive. b. Origin: This menu is displayed after the operator selects menu option 5 (“Erase Test Plan”) from the “Test Plan With Thumb Drive Menu” (Figure 81.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.14 Erase Thumb Drive Test Plan Status Displays ERASE THUMB DRIVE TP PLAN_ ERASE THUMB DRIVE TP PLAN_### Figure 90.0 Erase Thumb Drive Test Plan Status Displays a. Description: Allows the operator to enter a thumb drive test plan number to be erased. b. Origin: This menu is displayed after the operator selects 1 (“Erase Internal Tp”) from the “Erase Test Plan With Thumb Drive Menu” (Figure 89.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 25.15 Save Test Plan With Thumb Drive Menu 1.SAVE INTERNALLY . 2.SAVE TO THUMB DRIVE Figure 91.0 Save Test Plan With Thumb Drive Menu a. Description: Allows the operator to save a test plan to internal memory or to the thumb drive. b. Origin: This menu is displayed after the operator selects menu option 6 (“Save Test Plan”) from the “Test Plan With Thumb Drive Menu” (Figure 81.0). c.
TRI-PHASE OPERATING™ INSTRUCTIONS 26.0 Computer Interface Description 26.1 Computer Interface Status Display *** !DANGER! *** REMOTELY CONTROLLED. HIGH VOLTAGE MAY BE PRESENT. Figure 92.0 Computer Interface Status Display a. Description: Testing may be remotely controlled via an IBM-compatible PC through either an RS-232C port or through the USB port using the TTRA software application.
TRI-PHASE OPERATING™ INSTRUCTIONS 26.2 Emergency Turn Off Switch The emergency turn off button switch (Figure 1.0 and Table 4.0 index 2) provides for those situations where immediate removal of power output from the TRI-PHASE™ to the transformer under test is necessary for safety of the test personal. To immediately turn off output power from the TRIPHASE™ to the transformer under test push down on the button switch.
TRI-PHASE OPERATING™ INSTRUCTIONS 27.0 TRI-PHASE™ Firmware Programming Notes The TRI-PHASE™ firmware may be updated anytime by the users in the field. The current firmware revision is posted under “Downloads” on the Vanguard Instruments web site (www.vanguard-instruments.com). To request a copy of the TRI-PHASE™ firmware, select the “Downloads” option on the web site. The user is then required to fill out the request form.
TRI-PHASE OPERATING™ INSTRUCTIONS 27.0 TRI-PHASE™ Firmware Programming Notes (continued) Vanguard Instruments TRI-∅™ True Three Phase TTR MAIN CODE REV 1.008 Figure 95.0 Firmware Revision Menu 2 Vanguard Instruments TRI-∅™ True Three Phase TTR Oscillator Code Rev. 1.00 Figure 96.0 Firmware Revision Menu 3 Vanguard Instruments TRI-∅™ True Three Phase TTR VDRV REV 03.62/1.00 Figure 97.
TRI-PHASE OPERATING™ INSTRUCTIONS 27.0 TRI-PHASE™ Firmware Programming Notes (continued) Vanguard Instruments TRI-∅™ True Three Phase TTR S/N 20002 Figure 98.0 Firmware Revision Menu 4 Vanguard Instruments TRI-∅™ True Three Phase TTR OPERATION: 513 Figure 99.0 Firmware Revision Menu 5 Vanguard Instruments TRI-∅™ True Three Phase TTR Calibrating… Figure 100.
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX A TRANSFORMER VECTOR GROUP CODES Utility power transformers manufactured in accordance with IEC specifications have a Rating Plate attached in a visible location which contains a list of the transformer's configuration and operating specifications. One such rating is the winding configuration and phase-displacement code. This code follows a convention that comprises letter and number sets that denote three-phase winding configurations (i.e.
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B 142
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 143
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 144
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 145
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 146
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 147
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 148
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 149
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 150
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 151
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 152
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 153
TRI-PHASE OPERATING™ INSTRUCTIONS APPENDIX B (continued) 154
TRI-PHASE OPERATING™ INSTRUCTIONS 1520 S. Hellman Ave., Ontario, CA 91761, USA Phone: 909-923-9390 Fax: 909-923-9391 www.vanguard-instruments.com Rev 1 (10/2008 HPN) Copyright © 2008 by Vanguard Instruments Co.