When performing an OPEN-CLOSE
test, the breaker opens but will not
close.
Delay between OPEN to CLOSE is probably too short. Increase the
delay time.
No data or erratic reading on travel
transducer.
Bad transducer. Perform a transducer diagnostic test using the
instructions in section 4.2.
Transducer slider is not secured to timing rod.
Transducer is not secured properly.
No activity on “V2” or “V3” voltage
input channel.
The “V2” and “V3” voltage sensing input channels require a
voltage change greater than 30V.
How do I turn on automatic printing
of test reports?
Please see section 3.2.3.