Operating instructions
1010
Horizontal Termination Venting Confi gurations
See venting accessories list on pages 32–33 for allowable components.
Rear Outlet—No Vertical Rise
Flat on the Wall
Maximum 26” horizontal pipe length;
817VAK Vent Collar Adapter required if using other
than Valor’s 551DVK pipe with termination;
Terminal Guard may be required if terminating within
7’0” of grade or where accessible.
In Corner—No Vertical Rise
Maximum 1 x 45° elbow allowed;
Maximum 18” horizontal pipe length;
Terminal guard may be required if terminating within
7’0” of grade or where accessible.
•
•
•
•
•
•
Approved
trough wall
shield/thimble
Approved
side wall
termination
530
engine
Max. 26” (66 cm)
14” (36 cm) max.
within
combustible wall.
26” (66 cm) max.
vent length
Approved
through wall
shield/thimble
Approved
side wall
termination
530
engine
18” (46 cm)
max vent pipe