Unit installation

The flame height control does not have to be re-set every time the fire is lit. It can be
kept at any position enabling the customer to use the right hand control only to ignite
the burner at the set flame height.
After checking turn the right hand knob to off. Depress the control knob partially at the
pilot position ( ), turn clockwise to off (
•
) and release the knob. If any
resistance is felt when turning, release the downward pressure on the knob before
continuing to turn.
14.3 Checking inlet pressure.
The burner aeration is non-adjustable. The appliance is preset to give the correct heat
input on Natural Gas at 20 mbar (8in w.g) inlet pressure and no further adjustment is
necessary. The burner pressure should be checked at the pressure test point located
on the inlet ‘T’ connector (See figure 31). The pressure check should be carried out
using a calibrated pressure gauge after removing the test point screw. The fire should
be alight and the left hand control knob at its fully anticlockwise setting (Maximum
flame height). The pressure setting should be within the limits shown in section 2 of
this manual (Appliance data and efficiency). After checking the pressure, turn off the
fire, remove the pressure gauge and replace the pressure test sealing screw. Relight
the fire and test all gas joints for soundness using a suitable leak detection fluid.
INSTALLER GUIDE
Figure 31. Pressure test point