Specifications

7
Figure #3: Chimney Configuration Figure #4: Fireplace Frame
The table below shows the minimum chimney height requirements, fireplace included, according to the
number of elbows:
Chimne
y
Number of Elbows Minimum Hei
g
ht
Straight installatio
n
--------------- 15’ (4.6 m)
1 - 15° offset 2 - 15° elbows 15’ (4.6 m)
2 - 15° offsets 4 - 15° elbows 18’ (5.5 m)
1 - 30° offset 2 - 30° elbows 15’ (4.6 m)
2 - 30° offsets 4 - 30° elbows 20’ (6.1 m)
* 1 - 45° offset * 2 - 45° elbows 16’ (4.9 m)
* 2 - 45° offsets * 4 - 45° elbows 23’ (7.0 m)
* Permitted only in Canada.
FIREPLACE INSTALLATION
1. Before beginning installation, remove the fireplace trim to protect it from damage. The fastening screws are
located behind the upper and lower louvers. Make sure no masonry products or acids come into contact
with the trim as these may discolor the finish which is not under warranty.
2. Remove all combustible floor coverings, e.g. carpeting, linoleum, etc., from the area where the fireplace is
to be installed.