Specifications

8 947169
Connecting Speakers
1. Locate and mount all speakers in accordance with the floor plan drawing for
this installation.
2. Connect each speaker to the appropriate home run or speaker-to-speaker wiring
scheme as shown on the wiring plan (see Figure 10).
3. Test speaker wiring for short circuits.
Measure the resistance of each home run wire run with an ohmmeter. Any pair
indicating a value of less than 15 ohms must be rechecked for possible shorted
wiring or speakers. Correct any problems and retest.
Figure 10. Speaker Run Methods
R66B
R66B
SPEAKERS
66-TYPE
CONNECTION
BLOCK
HOME RUN METHOD
TWO
WIRES
TWO
WIRES
TWO
WIRES
SPEAKER TO SPEAKER METHOD
SPEAKERS
AMPLICENTER
AMPLICENTER
AmpliCenter D300
PagePac Plus
R
AmpliCenter D300
PagePac Plus
R
Note: If paging zones use the
talkback feature (available only
when used with PagePac
®
Plus
Controller), cabling must be
shielded and grounded at the
AmpliCenter connector, not the
speaker. Maximum 2 speakers per