Specifications

9
Connecting Speakers
1. Locate and mount all speakers in accordance with the floor plan drawing for this installation.
2. Connect each speaker to the appropriate home run or speaker-to-speaker wiring scheme as shown on the wiring plan (see
Figure 11).
3. Test speaker wiring for short circuits to ground and across speaker terminals.
4. Measure the resistance of each home run wire run with an ohmmeter. Any pair indicating a value of less than 16 Ohms -
D300A, 49 Ohms - D100A and 122 Ohms - D40 must be rechecked for possible shorted wiring or speakers. Correct any
problems and retest prior to turning on amplifier.
VALCOM
AMPLICENTER D300A
SPEAKER TO SPEAKER METHOD
HOME RUN METHOD
AMPLICENTER D300A
VALCOM
Note: If paging zones use the talkback feature (Available only when used with PagePac
®
Plus Controller), cabling must be shielded
and grounded at the AmpliCenter connector, not the speaker. Maximum 2 speakers per zone with talkback.
Figure 11. Speaker Run Methods.