Powering 
WMT700 has separate power supply inputs for operating and 
heating power. The inputs are usually connected to the same 24 
VDC power supply unit, but special applications such as battery 
operation or battery back-up may require separate supplies. 
The operating power has one supply terminal and one ground 
terminal, while the heating power has two supply terminals and 
two ground terminals allowing a higher supply current. All supply 
ground terminals are internally connected to each other. 
NOTE 
In a 
system setup with two separate power supplies, avoid ground 
potential differences between the supplies. Connect the negative 
terminals
 together if necessary. 
Operating Power 
WMT700 can use any 9 ... 36 V (nominal voltage 24 V) minimum 
2 W DC power supply that meets applicable safety regulations. 
Connect heating supply wires to the ground in case heating is not 
used. The typical current and power consumptions vs. operating 
voltage are shown in Figure 38 and Figure 39 on page 86. Note 
that the selected heating option affects the needed operation 
voltage when separate powering for operation and heating is used. 
Table 26  Operating Power Supply Voltage Requirements 
Used Heating Option 
Operating Power Supply 
None 
9 … 36 VDC 2 W 
Transducers 
12 … 36 VDC 2 W 
Transducers and arms 
14 … 36 VDC 2 W 
Transducers, arms and body 
16 … 36 VDC 2 W 
84 ___________________________________________________________________ M211095EN-E 