Limitations for Output Signals 
You can specify the minimum and maximum values for analog 
output with the configuration parameters. The output is fixed to 
the specified values, and the unit depends on the selected analog 
output mode. 
Example 
To limit the output 1 in voltage mode to a range of 0.1 … 5 V, set 
the analog output minimum value to 0.1 and the analog output 
maximum value to 5. Enter the following commands: 
S aout1minv,0.1 
S aout1maxv,5 
Missing Readings and Error Indication 
If WMT700 is not able to measure the wind, it indicates a missing 
reading in the output. The most common reasons for measurement 
problems are foreign objects (such as ice, birds, or other foreign 
object) on the line of measurement or sound reflections from 
nearby objects (such as wind tunnel walls). 
The default error indication is an out-of-range signal that is more 
than 10 V or 20 mA but other error settings can also be 
configured. 
Example 
To set analog output 1 error indication in voltage mode to 1 V, set 
the analog output error value to 1. Enter the following command: 
S aout1err,1 