TECHNICAL REFERENCE Upgrading from Vaisala Ultrasonic Wind Sensor WS425 to WMT700 M211097EN-C
PUBLISHED BY Vaisala Oyj P.O. Box 26 FI-00421 Helsinki Finland Phone (int.): +358 9 8949 1 Fax: +358 9 8949 2227 Visit our Internet pages at www.vaisala.com. © Vaisala 2011 No part of this manual may be reproduced in any form or by any means, electronic or mechanical (including photocopying), nor may its contents be communicated to a third party without prior written permission of the copyright holder. The contents are subject to change without prior notice.
________________________________________________________________________________ Table of Contents CHAPTER 1 GENERAL INFORMATION............................................................................ 7 About This Manual ................................................................... 7 Contents of This Manual ....................................................... 7 Version Information ............................................................... 8 Related Manuals ...............................
TECHNICAL REFERENCE___________________________________________________________ CHAPTER 5 OPERATING WMT700 WITH WS425 AND SDI-12 PROFILES..................41 Communication Profiles ........................................................41 Getting Started........................................................................42 Operating WMT700 with Terminal Program.........................42 Entering Configuration Mode ................................................44 WS425 F/G ASOS Profile .............
________________________________________________________________________________ APPENDIX A COMPLETE COMMAND SET FOR WMT700 .............................................
TECHNICAL REFERENCE___________________________________________________________ This page intentionally left blank.
________________________________________________________________________________ List of Figures Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 WMT700 Sensor Handling ....................................................... 14 WMT700 and Transportation Damper...................................... 15 WMT700 Retrofit Installation to Pole Mast............................... 17 WMT700 Retrofit Installation to Cross Arm with Array Facing Up .......
TECHNICAL REFERENCE___________________________________________________________ List of Tables Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Manual Revisions .......................................................................8 Related Manuals.........................................................................
Chapter 1 ________________________________________________________ General Information CHAPTER 1 GENERAL INFORMATION This chapter provides general notes for the manual and WMT701, WMT702, and WMT703. About This Manual This manual contains instructions for upgrading to Vaisala WINDCAP® Ultrasonic Wind Sensor series WMT700 and using analog output and serial communication in a system configured for WS425.
TECHNICAL REFERENCE___________________________________________________________ Version Information Table 1 Manual Code M211097EN-C M211097EN-B M211097EN-A Manual Revisions Description April 2011. This manual. Updated wiring instructions and added information on new ROSA analog cable. September 2010. Previous manual. Updated mounting instructions and illustrations. Updated names of accessories and cables. Previous version.
Chapter 1 ________________________________________________________ General Information Safety Vaisala WINDCAP® Ultrasonic Wind Sensor WMT701, WMT702, or WMT703 delivered to you has been tested for safety and approved as shipped from the factory. Note the following precautions: WARNING Make sure that you connect only de-energized wires.
TECHNICAL REFERENCE___________________________________________________________ This page intentionally left blank.
Chapter 2 _______________________________________________________________Introduction CHAPTER 2 INTRODUCTION This chapter provides general information on upgrading from WS425 to WMT700 wind sensor series. NOTE In this manual, product types WMT701, WMT702 and WMT703 are commonly referred to as WMT700. When upgrading to WMT700, you have the following installation options: - Basic installation procedure, which consists of mounting WMT700 with the FIX70 mounting kit and the WMT700 mounting adapter.
TECHNICAL REFERENCE___________________________________________________________ - To receive wind measurement data as current, potentiometer, voltage, or frequency output, use analog output. For general information, see Vaisala WINDCAP® Ultrasonic Wind Sensor Series WMT700 User's Guide. For instructions for systems configured for WS425, see Chapter 4, Operating WMT700 in WS425 Analog Output Mode, on page 33 in this manual.
Chapter 3 _________________________________________________________ Retrofit Installation CHAPTER 3 RETROFIT INSTALLATION This chapter describes the retrofit installation procedure for WMT700. Retrofit Installation Procedure At the measurement site, WMT700 needs to be mounted and connected to the power source and data acquisition system. After upgrading to WMT700, it is possible to install the optional bird prevention kit available for the wind sensor.
TECHNICAL REFERENCE___________________________________________________________ 1005-004 Figure 1 WMT700 Sensor Handling Unpacking Instructions WMT700 is shipped in a cardboard custom container with plastic transportation dampers. One of the dampers protects the wind sensor body, while the other shields the array and the transducers. See Figure 2 on page 15. When unpacking the wind sensor, remove the transportation damper that protects the sensor body.
Chapter 3 _________________________________________________________ Retrofit Installation Figure 2 below shows the damper protecting the array. 1005-025 Figure 2 NOTE WMT700 and Transportation Damper Save the container and all the packaging materials for future transporting or shipping.
TECHNICAL REFERENCE___________________________________________________________ Mounting You can mount WMT700 either to a vertical pole mast or a horizontal cross arm using a WS425 mounting kit. The procedure for both mounting options is identical. Typically you can upgrade from WS425 to WMT700 without removing the mounting kit. NOTE If you remove the mounting kit, you need to align the wind sensor after the mounting procedure.
Chapter 3 _________________________________________________________ Retrofit Installation 1104-081 Figure 3 WMT700 Retrofit Installation to Pole Mast The following numbers refer to Figure 3 above: 1 = WMT700 wind sensor 2 = Mounting adapter for FIX30/60 3 = WS425 mounting kit 4 = Mounting screw VAISALA _______________________________________________________________________ 17
TECHNICAL REFERENCE___________________________________________________________ 1104-082 Figure 4 WMT700 Retrofit Installation to Cross Arm with Array Facing Up The following numbers refer to Figure 4 above: 1 = WMT700 wind sensor 2 = Mounting adapter for FIX30/60 3 = Mounting screw 4 = WS425 cross arm 18 __________________________________________________________________ M211097EN-C
Chapter 3 _________________________________________________________ Retrofit Installation 1104-083 Figure 5 WMT700 Retrofit Installation to Cross Arm with Array Facing Down The following numbers refer to Figure 5 above: 1 = Mounting adapter for FIX30/60 2 = WS425 cross arm 3 = WMT700 wind sensor VAISALA _______________________________________________________________________ 19
TECHNICAL REFERENCE___________________________________________________________ Before You Start Before you start the retrofit installation procedure, make sure that you have the correct items: - Correct mounting kit (already attached to the mast) for retrofit installation. Figure 6 below shows the available options: FIX30 and FIX60. 1006-054 Figure 6 FIX60 (Left) and FIX30 (Right) For information on the FIX70 mounting kit, see Vaisala WINDCAP® Ultrasonic Wind Sensor Series WMT700 User's Guide.
Chapter 3 _________________________________________________________ Retrofit Installation - Correct mounting adapter for your installation; FIX30 or FIX60, see Figure 7 below. The diameter of the mounting adapter for FIX30/60 adapter is 61 mm. Change the mounting adapter if necessary. If you are not sure that you have the correct mounting adapter, contact Vaisala.
TECHNICAL REFERENCE___________________________________________________________ Table 3 Mounting Kits and Cable Codes 227567SP FIX70 In Out x x FIX30 In Out x FIX60 In Out x x 227568SP x x x x x 231425SP x x x x x 228259SP x x x x x 228260SP x x x x x 227565SP x x x x x 229807SP x x x x x 227566SP x x x x x Description Spare Part Item WMT700 Cables with open leads one end (Standard 2m/10m, RS485 2m/10m, ROSA analog 10m) WMT700 Cables with connectors on both
Chapter 3 _________________________________________________________ Retrofit Installation 4. 5. 6. Attach the WMT700 sensor body to the WS425 mounting kit and tighten the bolt. Remove the transportation damper protecting the array and store it for future use. Connect the cable to the data acquisition system and power supply. Connect the wires according to section Wiring on page 25. WMT700 is now ready for operation.
TECHNICAL REFERENCE___________________________________________________________ Check List for Connection Cables Take the following issues into account when installing WMT700: - Routing of the cables depends on the mounting option selected for WMT700. When mounting to a mast, the cable can be routed either outside or inside the mast depending on the mast type and other equipment (for instance, lightning rods) installed to the mast.
Chapter 3 _________________________________________________________ Retrofit Installation Wiring There are two ways of performing the WMT700 retrofit installation: - Using Standard WMT700 Cables - Using WS425 Cables with adapters When performing WMT700 retrofit installation, the possible cables depend on the selected mounting kit. For the FIX60 mounting kit, adapter cables are provided for the WS425 serial and analog output modes.
TECHNICAL REFERENCE___________________________________________________________ wires must be properly isolated and terminated to avoid unwanted operation or failure.
Chapter 3 _________________________________________________________ Retrofit Installation NOTE FIX30 is not compatible with adapter cables due to the small diameter of the mast. Adapter Cable for WS425 Serial Output The Adapter Cable for WS425 Serial (227569SP) can be used with the WS425 cables ZZ45203 and 010411. Table 5 below lists the adapter pin-outs and signal descriptions as they appear on their user guides for both WMT700 and WS425 connectors.
TECHNICAL REFERENCE___________________________________________________________ Table 6 Pin-Outs for WS425 Analog Frequency Output Adapter Cable WMT700 WMT700 Signal Connector Description Pin 1 Operating Power Supply 2 Analog Output AOUT2, Wind Direction 5 Heater Power Supply 7 Heater Power Supply Ground 11 Operating Power Supply Ground 12 Analog Output Ground 13 Analog Output AOUT1, Wind Speed 17 Reference Input for AOUT2 WS425 Connector Pin 11 +12 VDC WS425 Wire Color Brown 13 WD Vout Grey 16 +3
Chapter 3 _________________________________________________________ Retrofit Installation Table 7 Pin-Outs for WS425 Analog Voltage Output Adapter Cable WMT700 WMT700 Signal Connector Description Pin 1 Operating Power Supply 2 Analog Output AOUT2, Wind Direction 5 Heater Power Supply 7 Heater Power Supply Ground 11 Operating Power Supply Ground 12 Analog Output Ground 13 Analog Output AOUT1, Wind Speed 17 Reference Input for AOUT2 WS425 Connector Pin 11 +12 VDC WS425 Wire Color Brown 13 WD Vout Gre
TECHNICAL REFERENCE___________________________________________________________ Table 8 Analog Output Connections WMT700 WMT700 Signal Connector Description Pin 13 Analog Output AOUT1, Wind Speed 2 17 12 Analog Output AOUT2, Wind Direction Reference Input for AOUT2 Analog Output Ground Voltage Output WS425 Connector Pin, Wire Color Voltage Current 15: Violet (connect pin 14 to ground) not available Frequency 14, Pink Voltage Current Potentiometer Potentiometer 13, Grey not available 13, Grey 12, Wh
Chapter 3 _________________________________________________________ Retrofit Installation NOTE When WMT700 is in operation, the power consumption is higher than with WS425. This can affect system performance in power-critical applications such as solar-powered or battery-powered systems. Use solar-powered or battery backup only to secure operating voltage. Ensure that the solar-powered system has a sufficient power reserve available.
TECHNICAL REFERENCE___________________________________________________________ This page intentionally left blank.
Chapter 4 _______________________________ Operating WMT700 in WS425 Analog Output Mode CHAPTER 4 OPERATING WMT700 IN WS425 ANALOG OUTPUT MODE This chapter provides information on operating WMT700 in analog output mode in a system configured for WS425. NOTE For general information on operating WMT700 with analog output, see Vaisala WINDCAP® Ultrasonic Wind Sensor Series WMT700 User's Guide.
TECHNICAL REFERENCE___________________________________________________________ Table 10 Parameter Name Required Parameters for WS425 Analog Output Operation Mode Allowed Values Description aoErrValue Default Value 1000 0 …. 32000 Set 2 for voltage output and 1000 for frequency output for similar operation as with WS425. aout1_g 1 0 …. 100 aout2_g 1 0 …. 100 Gain for AOUT1. Set 0.01789 for compatibility with WS425 voltage output. Set 11.18 for compatibility with WS425 frequency output.
Chapter 4 _______________________________ Operating WMT700 in WS425 Analog Output Mode Wind Speed Output In a system configured for WS425, you can set WMT700 to measure wind speed and send analog output as frequency or voltage. The sections below describe WMT700 analog output when: - Settings are configured according to Table 10 on page 34. - Wires are connected according to section ROSA Cable 10m (Analog Outputs) on page 25.
TECHNICAL REFERENCE___________________________________________________________ 0212-039 Figure 10 Wind Speed Frequency Analog Output with WS425 Cable and Adapter Cable for Analog Frequency Output Voltage When voltage is selected as the wind speed analog output, the output from WMT700 varies linearly from 0 VDC at 0 miles per hour to 1 VDC at 125 miles per hour or 100 mV/m/s. In SI units, the voltage varies linearly from 0 VDC at 0 meters per second to 1 VDC at 55.88 meters per second.
Chapter 4 _______________________________ Operating WMT700 in WS425 Analog Output Mode 0212-038 Figure 11 Wind Speed Voltage Analog Output with WS425 Cable and Adapter Cable for Analog Voltage Output Wind Direction Output When wind direction is measured, WMT700 sends analog output as simulated potentiometer output voltage referred to as external reference voltage. The output is a proportional signal 0 ... 100 % of the reference voltage representing the wind direction.
TECHNICAL REFERENCE___________________________________________________________ 0212-040 Figure 12 Wind Direction Voltage Output with WS425 Cable and Adapter Cable Limitations for Output Signals You can specify the minimum and maximum values for analog output with the configuration parameters. The output is fixed to the specified values, and the unit depends on the selected analog output mode. Example To limit the output 1 in voltage mode to a range of 0.1 … 5 V, set the analog output minimum value to 0.
Chapter 4 _______________________________ Operating WMT700 in WS425 Analog Output Mode Missing Readings and Error Indication If WMT700 is not able to measure the wind, it indicates a missing reading in the output. Most common reasons for measurement problems are foreign objects (such as ice, birds, or other foreign object) on the line of measurement or sound reflections from nearby objects (such as wind tunnel walls).
TECHNICAL REFERENCE___________________________________________________________ This page intentionally left blank.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles CHAPTER 5 OPERATING WMT700 WITH WS425 AND SDI-12 PROFILES This chapter provides information for operating WMT700 in serial operation mode with WS425 or SDI-12 profiles. In this chapter each communication profile has its own section listing the configurable parameters and the available commands and data messages.
TECHNICAL REFERENCE___________________________________________________________ Getting Started The communication profile and other settings have been configured at the factory according to the customer specifications given when ordering the product. You can start using WMT700 directly after the installation with these settings. In case you want to change the communication profile, you must also check the other required parameters and change them if necessary.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles For the correct settings for SDI-12 profile, see section SDI-12 on page 60. 7. 8. 9. 10. 11. Click Apply and OK. On the Settings tab, click ASCII setup. Select ASCII sending Send line ends with line feed (optional). Click OK and close the New Connection Properties window. On the View menu, click Font. In the Font list, select Terminal. From the Call menu, click Call.
TECHNICAL REFERENCE___________________________________________________________ Entering Configuration Mode This command switches the serial port to configuration mode. The command works with any communication profile supported by WMT700. $aOPEN where $ a = = = = Fixed text. Value of the address parameter. If the value is 0, it refers to any WMT700 address. Carriage return. Line feed.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles Table 11 Parameter Configurable Parameters for WS425 F/G ASOS Profile Default Value 0 Profile-specific Allowed Values 0 = automatic messages disabled com1_protocol com2_protocol (depending on the port used for operating WMT700) wndAvg 0 2 = WS425 F/G ASOS 1 wndGustTime 3 wndOrientation 0 wndUnit 0 0.25 … 3600 Resolution: 0.25 0.25 … 3600 Resolution: 0.
TECHNICAL REFERENCE___________________________________________________________ The WA command is executed by the ASOS at an interval that ranges from 1 to 30 seconds. For the WA command, WMT700 responds to the ASOS interrogation poll within 250 milliseconds of receiving the request. NOTE The following WS425 F/G ASOS commands cannot be used with WMT700: WB, WFIRMWARE, WJ, WD, WF, WR, WCAL, WH, WT, WCDV, WSTK, WL, WM, WN, WSST, and WATE. WMT700 can only be configured in the configuration mode.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles indication is given with the single character P or F. This is followed by the description of the measured parameter, which is followed by the actual measured value. The Bad 1 second readings counter is a running total of the number of fundamental 1-second readings that the sensor flagged as bad. This number rolls over to zero after reaching the count value of 65535.
TECHNICAL REFERENCE___________________________________________________________ WS425 F/G ASOS Data Message WMT700 responds to the WA command with a data message described in Table 13 below. Table 13 Byte 1 2 3 4 5-7 8-10 11-12 13-14 15-19 20-24 25 26-27 28-29 30 31 32 WS425 F/G ASOS Data Message Description Start of text Sensor ID Command identifier Sensor status: P = Pass F = Fail H = Heater failure For further information, refer to notes 1 and 2.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles For example, a value of 99 signifies that all data samples were determined to be valid and processed during the averaging time. If some samples were determined to be "missing", these samples were not processed and the reported signal quality is a proportional value less than 99. 4. Bytes 28-29 are the modulo 256 hexadecimal checksum of the ASCII values calculated for bytes from 2 to 27. Example: WAP2131870503012.
TECHNICAL REFERENCE___________________________________________________________ Table 14 Parameter Configurable Parameters for WS425 A/B NMEA Standard Profile address Default Value 1 Profile-specific Allowed Values String with 1 character autoInt 1 0.25 ... 1000 Resolution: 0.25 autoPort 1 autoSend 0 com1_protocol com2_protocol (depending on the port used for operating WMT700) wndAvg 0 wndOrientation 0 wndUnit 0 wndVector 1 1 Description Address for WMT700.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles where NOTE [ = = = = * = = = = Reference: R = relative T = true Wind speed Wind speed unit: K = kilometers per hour M = meters per second N = knots Status: A = data valid V = invalid data Fixed text Checksum (8-bit XOR, excluding $ and *) Carriage return code, ASCII 0DH Line feed code, ASCII 0AH When the NMEA Standard profile is selected, the autoInt parameter must have]
TECHNICAL REFERENCE___________________________________________________________ Table 15 Parameter Configurable Parameters for WS425 A/B NMEA Extended Profile address Default Value 1 Profile-specific Allowed Description Values String with 1 character Address for WMT700. autoInt 1 0.25 ... 1000 Resolution: 0.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles WS425 A/B NMEA Extended Commands This command polls data from WMT700.
TECHNICAL REFERENCE___________________________________________________________ WS425 A/B NMEA Extended Data Message WS425 A/B NMEA Extended data message is as follows: $PMWV,,[,,,* where $P MWV ][ = = = = = = = = * = = = = Fixed text Data ID; A … Z Fixed text Wind angle: 0 to 359 degrees Reference: R = relative T = true Wind speed Wind speed unit: K = kilometers per hour M = meters per second N = knots Status:]
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles WS425 A/B ASCII Profile In Vaisala WINDCAP® Ultrasonic Wind Sensor WS425 User's Guide, this profile was called the Handar mode. NOTE Configurable Parameters Table 17 below lists the configurable parameters and their allowed and default values for the WS425 A/B ASCII Profile. Table 17 Parameter Configurable Parameters for WS425 A/B ASCII Profile autoInt Default Value 1 Profile-specific Allowed Values 0.25 ...
TECHNICAL REFERENCE___________________________________________________________ WS425 A/B ASCII Commands Table 18 below lists the available commands for operating WMT700 with the WS425 A/B ASCII profile. Table 18 Command I Wx NOTE List of WS425 A/B ASCII Commands Description Requests identification information for WMT700. Starts measurement based on averaging time and fetches the data.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles WMT700 responds to the Wx command with a 19-character fixed-length data message. For more information, see Table 19 below. Table 19 Character 1 Description ┐ 02H (, start of transmission) 2 3 4 W Averaging in seconds.
TECHNICAL REFERENCE___________________________________________________________ Interpretation of the example message: - 02H (, start of transmission) Sensor ID: W Averaging in seconds: 5 Sensor status: P = pass Wind direction: 120 Wind speed: 0013 .
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles WS425 A/B WAT11 Commands When the WS425 A/B WAT11 profile is selected, you can poll data using the following command: where = Escape character ASCII 27H = The WMT700 ID, for example, A The response is the following: where = Start of text character (1 digit) = The WMT700 identification character, for example, A (one digit).
TECHNICAL REFERENCE___________________________________________________________ SDI-12 Profile (v 1.3) SDI-12 is a standard for interfacing data recorders with microprocessorbased sensors. The name stands for serial/digital interface at 1200 baud. The SDI-12 Support Group is an association of companies that produce and use SDI-12 products with the purpose of reviewing requests to enhance, clarify, or modify the SDI-12 architecture and that votes on proposed changes to SDI-12.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles Configurable Parameters Table 21 below lists the configurable parameters and their allowed and default values for the SDI-12 profile. Table 21 Parameter Configurable Parameters for SDI-12 Profile address autoPort Default Value 1 1 Profile-specific Allowed Description Values 1, 2, 3, 4, 5, 6, 7, 8, 9 Address for WMT700. 2 = COM2 port Serial port to which WMT700 sends automatic data messages.
TECHNICAL REFERENCE___________________________________________________________ SDI-12 Commands Table 22 below lists the available commands for operating WMT700 with SDI-12 profile. NOTE You can only use COM2 serial port for sending commands and receiving data messages with the SDI-12 profile. Table 22 Command ?! a! aI! aAb! aC! aCC! aD0! aM! aMC! aV! List of SDI-12 Commands Description Queries WMT700 for its address. Ensures that WMT700 is responding.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles ?! — Address Query This command queries for the WMT700 address. When you use a question mark (?) as the address character with the a! command, WMT700 responds as if it was being addressed on the SDI-12 bus. Regardless of its address, WMT700 responds to the command, which allows you to determine the address for the wind sensor.
TECHNICAL REFERENCE___________________________________________________________ a! — Acknowledge Active This command ensures that WMT700 is responding to a data recorder or another SDI-12 device. It asks the WMT700 to acknowledge its presence on the SDI-12 bus. a! where a = ! = The single-digit WMT700 address that corresponds to the first character of the address value. Terminates the command.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles aAb! — Change Address This command changes the WMT700 address. After WMT700 has received this command and sent a response, the sensor does not respond to any other command for one second. This gives WMT700 time to write the new address to the non-volatile memory. NOTE You can also change the WMT700 address by entering configuration mode and changing the address parameter.
TECHNICAL REFERENCE___________________________________________________________ The response is the following: atttnn where a = ttt = nn = = The single-digit WMT700 address that corresponds to the first character of the address value. The period of time, in seconds, after which WMT700 has the measurement ready. The number of measurement values WMT700 calculates and returns as a response to one or more subsequent aD0! commands. Terminates the response.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles aD0! where a = D0 ! = = The single-digit WMT700 address that corresponds to the first character of the address value. The send data command. Terminates the command. For a description of the data messages, see section SDI-12 Data Messages on page 70. aI! — Send Identification This command queries WMT700 for its SDI-12 compatibility level, model number, and firmware version number.
TECHNICAL REFERENCE___________________________________________________________ aM! — Start Measurement This command starts measurement. WMT700 does not return measurement data after this command. It sends a response that indicates when the measurement result can be retrieved using the aD0! command and the number of parameters. aM! where a = M ! = = The single-digit WMT700 address that corresponds to the first character of the address value. The start measurement command. Terminates the command.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles aV! — Start Verification This command starts verification. However, WMT700 does not return verification data directly after this command. It sends a response that specifies when the verification results can be retrieved using the aD0! command and the number of parameters. The WMT700 verification data includes a watchdog count, sensor measurement unit settings, and the current SDI mode setting.
TECHNICAL REFERENCE___________________________________________________________ SDI-12 Data Messages When SDI-12 profile is selected, the data message sent by WMT700 depends on the command that you use before fetching the data with aD0! command.
Chapter 5 ______________________________ Operating WMT700 with WS425 and SDI-12 profiles WS425 A/B SDI-12 Message for V Command When you have given the commands aV! and aD0!, the response is the following: a where a = = The single-digit WMT700 address that corresponds to the first character of the address value. The number of times the watchdog has triggered. Ideally should be zero. Format: +(c)c Wind speed unit.
TECHNICAL REFERENCE___________________________________________________________ Example of the command and response: 1MC! 10025 1D0! 1+2.7+85.2-0.2-2.7+770.
Chapter 6 ___________________________________________________________ Troubleshooting CHAPTER 6 TROUBLESHOOTING This chapter describes common problems, their probable causes and remedies, and provides contact information for technical support. Problem Situations Table 23 below lists some problems situations that can occur during or after retrofit installation. For general troubleshooting instructions, refer to Vaisala WINDCAP® Ultrasonic Wind Sensor Series WMT700 User's Guide.
TECHNICAL REFERENCE___________________________________________________________ Technical Support For technical questions, contact the Vaisala technical support by e-mail at helpdesk@vaisala.com. Provide at least the following supporting information: - Name and model of the product in question Serial number of the product Name and location of the installation site Name and contact information of a technically competent person who can provide further information on the problem.
Appendix A _________________________________________ Complete Command Set for WMT700 APPENDIX A COMPLETE COMMAND SET FOR WMT700 Table 24 below lists all the commands available for WMT700.
TECHNICAL REFERENCE___________________________________________________________ Configuration Mode/ Measurement Mode and Profile Measurement mode WMT700 profile Measurement mode WMT700 profile Measurement mode WMT700 profile Measurement Mode MES12 profile Measurement mode WS425 ASOS F/G profile Measurement mode WS425 ASOS F/G profile Measurement mode WS425 A/B NMEA Extended profile Measurement mode WS425 A/B ASCII profile Measurement mode WS425 A/B ASCII profile Command Description Further Information OP
Appendix A _________________________________________ Complete Command Set for WMT700 This page intentionally left blank.
www.vaisala.