User Manual
Chapter 3 ____________________________________________________________ Getting Started
VAISALA_______________________________________________________________________ 45
Dependency of Wizard Calculations
Intervals
Table 5 on page 45 lists the Wizard calculation intervals that are
dependent on one another.
Table 5 Wizard Calculations Intervals
Function Inputs Interval Note
Air temperature
measurement
QMH101/102 10 s 1 min average used as instant
value for further processing and
reporting (TAStat1m).
Relative humidity
measurement
QMH101/102 10 s 1 min average used as instant
value for further processing and
reporting (RHStat1m).
Barometric pressure
measurement
PMT16A 10 s 1 min average used as instant
value for further processing and
reporting (PAStat1m).
Rain measurement QMR101/102 60 s
Global radiation
measurement
QMS101/102 or CM6B 10 s 1 min average used as instant
value for further processing and
reporting (SRStat1m).
Net radiation
measurement
QMN101 10 s 1 min average used as instant
value for further processing and
reporting (NRStat1m).
Soil/Water temperature
measurement
QMT103/110 10 s 1 min average used as instant
value for further processing and
reporting (TGStat1m).
Wind measurement QMW101/110 1 s
Dewpoint temperature
calculation
QMH101/102 60 s
Frostpoint temperature
calculation
QMH101/102 60 s
Heat index calculation QMH101/102 60 s
QFE calculation PMT16A
QMH101/102
Pslevel setting
60 s Pressure sensor level [m] is set
using AWS Client Common
parameters window; see Vaisala
HydroMet™ Data Collection
Platform User’s Guide, Volume 1,
section Modifying Station Settings.
QFF calculation PMT16A
QFE calculation
QMH101/102
Altitude setting
60 s Station altitude [m] is set using
AWS Client Common parameters
window; see Vaisala HydroMet™
Data Collection Platform User’s
Guide, Volume 1, section Modifying
Station Settings.