Technical data
8 Installation procedure 
8.2 Secondary system Pipework
•
Connect the two cold water control valves together as
shown in fig 11., ensuring that the orientation of the
valves, when installed in the cold mains supply, allows
the 15 mm outlet of the expansion relief valve to be
connected to the tundish.
Note:
The Expansion relief / non return valve has a 
R 3/4 connection, and is supplied fitted with a
PTFE ring to ensure a watertight seal when
screwed into the pressure limiting valve (separa-
te instructions are supplied with the control val-
ves).
•
Provide a cold water mains supply to the VANTAGE.
To ensure optimum performance from the VANTAGE,
and particularly in installations where the balanced
pressure cold water outlet (2, fig. 11) is to be used, the
pipework provided from the building mains stop valve
to the VANTAGE cylinder should be minimum 22 mm
copper tube.
•
Install the assembled cold water control valves (fig. 11)
in the cold mains supply at a convenient position adja-
cent to the VANTAGE cylinder, ensuring adequate
space exists for service access.
Important
No valve shall be installed between the assemb-
led cold water control valves and the cylinder.
Vaillant Vantage 120/150/20022
Fig. 10
 3 port
diverter valve
Balancing
valve
position
VIH 367/1
Fig. 11
1
3
2
VIH 368/1