Technical data
53
Does yellow hot water
demand indicator ( ) glow?
Check hot water flow rate
and temperature. Compare
with techncal data. The max.
temperature increase is
obtained with D.H.W.
thermostat on position 9. If
flow rate is not sufficient,
check imcoming main water
supply.
Normal operation carry out
electrical safety checks (see
section 5.1 preliminary
electrical checks).
Check D.H.W. operation
Sheet J
Does actuating lever operate
D.H.W. microswitch on
diverter valve/water section
assembly?
Check cold water inlet
pressure is sufficient. Check
filter in cold water inlet is
clean.
Check cold water isolating
valve (3, fig. 50) is fully
opened (turn anticlockwise).
Does lever move now?
Yes
No
Draw hot water at high rate.
Check/replace
D.H.W. microswitch.
Check/clean diaphragm and
venturi in the bottom part of
the diverter valve/water
section, replace as necessary.
Replace diverter section.
No
No
No
Yes
Yes
Yes