Technical data
52
Does yellow flame indicator
( ) glow and flames increase
in size to full rate?
Does burner flame modulate/
go out when maximum
radiator temperature control
is turned down to position 1
at a flow temperature of
approx. 50 degree C?
Check potentiometer for
partial load setting (see 5.9
C.H. range rating).
Pull of cable from NTC and
short-circuit to earth. Is flame
extinguished?
Check operation of burner and modulation
Sheet H
Check plug-in connections
to modulating solenoid.
Replace modulating regulator
of gas valve if burner still fails
to increase to full rate.
Yes
No
No
No
Replace electronic boards.
Go to sheet J.
Yes
Is flame extinguished after
2nd ignition attempt, and red
lockout indicator ( ) lit?
Is flame visible prior to
lockout condition?
Check gas supply is live and
purged.
Check connections/operation
of both solenoids, replace gas
valve as necessary.
Yes
No
No
Check/clean burner,
ionization sensor and cable
for defects, good contacts
and correct position.
Check air/flue gas system is
correctly fitted and not
obstructed. If lockout occurs
replace electronic boards.
Yes