Technical data
49
Does fan run?
Does yellow fan operation
indicator ( ) flash?
Does yellow flame
indicator ( ) flash?
Does yellow fan operation
indicator flash or glow?
Check air/flue gas system is
correctly fitted and not
obstructed. Check pitot tube
(in fan outlet) and air hoses
are not obstructed and are
correctly aligned. Check or
replace air pressure switch.
Check fan/flue gas system
Sheet E
Is 230 V present across
fan terminals?
Does yellow central heating
demand indicator ( )
glow?
No heat demand.
Go to sheet C.
Check/replace fan.
Yes
No
Yes
Yes
No
No
No
No
Yes
Switch main on/off control off
and on again.
Yes
Check NTC. Disconnect NTC lead at plug (3, fig. 37).
Does fan run now?
Check connection to NTC
temperature sensor, clean and
tighten. Check NTC not
shortened to earth. If O.K
replace NTC sensor.
Replace electronic boards.
No
Yes
Does yellow flame
indicator ( ) glow?
Defective electronic
boards.
No
Does burner light?
Yes
Go to sheet F.
No
Go to sheet H.
Yes
Yes
Does yellow flame
indicator ( ) flash?
No
Check pitot tube (in fan outlet)
and air hoses are not
obstructed and correctly
aligned. Check or replace air
pressure switch.
Yes
Does fan run now?
No
Yes
No